Our business model is flexible and we have become a strategic partner of many manufacturers and have a high reputation in the 40A Transformer DC Resistance Tester, turbine oil filtration machine, portable oil filtration systems industry. The products provided by the company provide a wealth of products for users in the industry and meet the comprehensive needs of users. We insist on cultural confidence and spiritual rise, and practice the people-centered development concept.
1. Introduction & Application
Transformer DC resistance is a must-test item for semi-finished products in finished transformer manufacturing, finished product testing, installation, overhaul, change of tap-changer, handover test and preventive test in the power sector.
It is able to check the welding quality of the winding joint and the presence or absence of the turn-to-turn short circuit of the winding, and it is possible to detect whether the contact of each position of the voltage tap changer is good and whether the actual position of the tap changer and the indicated position are consistent, whether the lead wire is broken, and the multi-strand wire is wound. Whether there are broken shares and so on.
In order to meet the needs of rapid measurement of DC resistance of transformers, FUOOTECH developed FTDC-100A DC resistance tester. The whole machine is controlled by high-speed single-chip microcomputer with high degree of automation and automatic discharge and discharge alarm function. The instrument has high test accuracy and easy operation, and can realize rapid measurement of the direct resistance of the transformer.
2. Security Measures
1). Be sure to read this manual carefully before using this instrument.
2). The operator of the instrument should have common knowledge of the use of general electrical equipment or instruments.
3). This instrument can be used indoors and outdoors, but should be used away from rain, corrosive gas and other places.
4). The instrument should avoid severe vibration.
5). Maintenance, care and adjustment of the instrument should be carried out by professionals.
6). After the test is completed, be sure to wait for the discharge alarm sound to stop before turning off the power and remove the test line.
7). To measure the no-load voltage regulating transformer, be sure to switch the gear position after the discharge indicating alarm sound stops.
8). During the test, it is forbidden to move the test clip and power supply line.
3. Technical Parameters
1). The output current: 100A, 50A, 20A, 10A, 5A
2). The minimum resolution: 0.1μΩ
3). Range: 100A: 50μΩ~100mΩ, 50A: 100μΩ~200mΩ
20A: 200μΩ~800mΩ, 10A: 500μΩ~2Ω, 5A: 1mΩ~4Ω.
4). Accuracy: ± (0.2% + 2 words)
5). Weight: 15KG without test line
4. Precautions
1). It is necessary to wait for the discharge to end. After the alarm sound stops, the line is removed again, otherwise it is dangerous.
2). When measuring the unloaded voltage regulating transformer, the discharge must be reset before the reverse tapping, and the switch point can be switched after the alarm sound stops.
3). When selecting current, refer to the range in the technical index column. When the current is over-range, the instrument is always in the "charging" state because the current does not reach the preset value. At this time, press the reset button to reset the instrument and re-select the smaller one. Current gear. When the range is under-balanced, "Current current is too small" is displayed. When these two states occur, the range is confirmed and a larger current is selected for testing.
4). After the test is completed, press the "Reset" button, the instrument power will be disconnected from the winding, discharge at the same time, the audible alarm, the ammeter will return to the zero position, then the display will return to the initial state, and the discharge can be rewired after the end of the discharge. Take the next measurement or remove the test line and the power cord to end the measurement.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. FAQ
Q1. Are you a manufacturer, trading company or a third party? When and where did your factory established?
FUOOTECH: We are a manufacturer established since 2002, located at Chongqing city, China.
Q2: Can you produce your products as our requirements, such as put on our logo?
FUOOTECH: Yes, OEM and ODM are available. We have the professional technical team to design the products as per your request.
Q3. What's the minimum order quantity?
FUOOTECH: 1 Set.
Welcome to contact us for any inquiry and cooperation.
We are capable of developing different 10A 20A 50A 100A Transformer Inductive Load DC Resistance Fast Tester to supply the best quality products and service to the customers. Our high quality products and reasonable price have been widely approved by our customers both in home and abroad. We believe that integrity is the foundation of all cooperation, tolerance is the premise of solving problems, innovation is a sharp tool for development and service is the basis for creating value. We effectively cultivate customer loyalty, achieve customer retention and management of customer lifetime value.
Hot Tags: 100a transformer dc winding resistance tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, Automatic Water Soluble Acid Tester, CT Analyzer, diesel oil filtration systems, vacuum oil filter, transformer vector group test set, transformer oil regeneration plant