We attach importance to green and sustainable development, and constantly innovate and develop new environmental protection Offline hydraulic oil filtration systems, lube oil purification system, Transformer Loss Tester. Our clients mainly distributed in the North America, Africa and Eastern Europe. The company develops new products based on customer needs, makes continuous contributions to the development of the industry, and strives to become a century-old enterprise. Our company will produce satisfactory products for you with standard business operation process and competitive price. We actively practice corporate social responsibility to achieve sustainable, rapid and healthy development of the enterprise.
1. Application
FTD-6000 Transformer Tan Delta and Capacitance Tester is a new generation test instrument for power industry, which fully automatic on-site measuring dielectric loss (tgδ) and the capacitance (Cx) of electric equipment. It's suitable for testing on transformer, insulating bush, capacitor, CT/PT, MOA etc.
It's also called: Automatic Capacitance and Tan Delta Tester, Capacitance and Dissipation Factor Tester, Capacitance & Dissipation Factor Test Set, Capacitance & Dielectric loss (Tan Delta) measuring bridge, Capacitance & Dissipation Factor Measuring Bridge
2. Dissipation/Power Factor Measurement (Tan Delta) on Instrument Transformers
An insulation failure is often the reason for an instrument transformer (IT) malfunction.
Factors which possibly accelerate the insulation's aging process:
● Moisture ingression due to broken seals
● Heat caused by the ambient temperature or sunlight
Older insulation can lead to high losses in the IT, which generates further heat. Since ITs are not actively cooled, old or degraded insulation can result in a failure or even an explosion. Fragments from the explosion represent a serious hazard for persons in the substation as well as for surrounding equipment.
Dissipation/power factor (tan(δ) delta) measurements help you determine the insulation condition. When using our transformer testing systems, you will also be able to determine the dissipation factor at various frequencies and detect any signs of aging at an early stage. Thus, an IT can be replaced before any further damage occurs.
3. Technical Parameters
Working condition |
-15℃~40℃ |
RH<80% |
|
Anti-interference principle |
Frequency conversion |
||
Power supply |
AC 85V~160V |
Generator can be used |
|
High voltage output |
0.5kV~12kV |
Every 0.1kV |
|
Precision |
2% |
||
Maximum current |
200mA |
||
Capacity |
2000VA |
||
Self-excitation power |
AC 0V~50V/15A |
45HZ/55HZ 47.5HZ/52.5HZ |
|
Resolution |
tgδ: 0.001% |
Cx: 0.001pF |
|
Accuracy |
△tgδ: ±(Reading*1.0%+0.040%) |
||
△Cx: ±(Reading*1.0%+1.00PF) |
|||
Measurement range |
tgδ |
Without limit |
|
Cx |
15pF < Cx < 300nF |
||
12kV |
Cx < 30 nF |
||
5kV |
Cx <150 nF |
||
1kV |
Cx <300 nF |
||
CVT test |
Cx < 300 nF |
||
CVT ratio range |
10~10000 |
||
CVT ratio accuracy |
0.1% |
||
CVT ratio resolution |
0.01 |
||
Storage |
200 group supports U disk data storage |
||
Dimension |
Main unit: 350(L)×270(W)×270(H) |
||
Accessory box: 350(L)×270(W)×160(H) |
|||
Weight |
Main unit: 22.75kg |
||
Accessory box: 5.25kg |
4. Features
1). Adaptive lithium batteries or 220 v ac supply. After a single charge, the dc resistance of hundreds of transformers can be tested continuously. The test process is simple and convenient
2). The output current is six grades, the maximum output current is 10A, the maximum output voltage is 25V, and the current can be automatically selected, which is convenient and fast.
3). Wide range and high accuracy,500uΩ~50KΩ.
4). It has the function of resistance temperature conversion, and can be equipped with wireless temperature measurement module, which can measure the field test temperature in real time to ensure the accuracy of resistance commutation value.
5). It has many kinds of protection functions, such as back EMF protection, broken line protection, power-off protection and over heating alarm.
6). 5.6-inch super industrial high-brightness color LCD screen, still visible under strong sunlight.
7). Equipped with external printer, facilitate data printing
8). It can be stored locally and on USB memory.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. FAQ
Q1. Are you a manufacturer, trading company or a third party? When and where did your factory established?
FUOOTECH: We are a manufacturer established since 2002, located at Chongqing city, China.
Q2: Can you produce your products as our requirements, such as put on our logo?
FUOOTECH: Yes, OEM and ODM are available. We have the professional technical team to design the products as per your request.
Q3. What's the minimum order quantity?
FUOOTECH: 1 Set.
Q4. Will the products be tested before shipping?
FUOOTECH: Yes, of course. QC personal will have a strict testing procedure to all the products before shipping.
As always, we will provide you with the best products at the best price, as well as technical moulding and finishing services at all times to meet your ever-changing needs for 10kv 12kv Anti Interference Transformer Tan Delta Dielectric Loss Tester with Thermal Printer. On the basis of summarizing the existing technologies at home and abroad, we adopted innovative technologies, obtained customer recognition and achieved good economic benefits. Our company has established a responsible, orderly, continuous and effective quality management system in the whole production process, which ensures the quality of our products.
Hot Tags: automatic anti-interference transformer tan delta and capacitance tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, mobile oil treatment, 10kv electrical insulation resistance tester, transformer oil regeneration system, Automatic Tensiometer, flash point tester, Transformer Loss Tester