We always insist on taking quality and technological innovation as the core competitiveness of enterprise development. We have won praises from customers all over the world for our excellent Lubricating Oil Filtration System, turbine oil dehydrator, oil filter cart quality and efficient service. We actively participate in social welfare undertakings and make unremitting efforts to build a harmonious society together within our capacity. We actively promote the construction of corporate culture and build a learning organization. Our company is based on the global market, closely combined with the characteristics of the industry, digging deep into the market application. We are proud of the fact that we have created true lasting partnerships with our customers. It is a core value of our company and a key element of what makes us successful in what we do.
1. Introduction & Application
FT-YJS-058 Automatic Insulating Oil Dielectric loss and electrical resistivity tester is used for measuring dielectric dissipation factor and DC resistivity of insulating oil and other insulating liquids. The instrument integrates with test oil cell, temperature controller, temperature sensor, dielectric loss test bridge, AC test power, standard capacitor, high resistance meter, DC high voltage source and other major components.
Transformer oil dielectric loss testing equipment is used both at the stage of checking the quality of oil before feeding it into the transformer and during the use of oil in the transformer.
The primary enemies of transformer oil are oxidation, contamination, and excessive temperature. High values of Tan Delta commensurate with reduced levels of Resistivity indicate the presence of polarised contaminants, such as moisture, particles and fibres. This testing is a sensitive way to check for contamination when purchasing unused new oil, determining the progress of the oil purification process and for quality control of oil in service.
2. What Is Tan δ, Or Tan Delta? What is Resistivity?
Tan Delta, also called Loss Angle or Dielectric Dissipation Factor (DDF) or Power Factor (PF) testing, is an electrical dielectric test on the insulating oil used to determine its quality. The test is performed at two temperatures. Information from each test and the results considered together may form the basis for making a judgment on whether it's suitable for a transformer to continue in service and for determining when the replacement or regeneration of the transformer oil is needed.
Resistivity is another indicator of oil's electrical quality, particularly apropos for used oil. Resistivity is an intrinsic property that quantifies how strongly a given material opposes the flow of electric current. A low resistivity indicates a material that readily allows the movement of electric charge. For a DC resistivity measurement, a specified DC voltage is applied to the cell, and after one minute, the current flowing between the electrodes is measured. Average resistivity values are calculated from readings taken after direct and reverse polarity. It is noted that cell electrodes should be short-circuited for a prescribed amount of time (which may vary by standard) between direct polarity and reverse polarity measurements and also between Tan Delta and resistivity measurements.
3. Technical Parameters
Voltage supply |
AC 220V±10% |
Power frequency |
50Hz/60Hz ±1% |
Measuring range |
|
Capacitance |
5pF~200pF |
Relative Permittivity |
1.000~30.000 |
Dielectric loss factor |
0.00001~100 |
DC Resistivity |
2.5MΩm~20TΩm |
Measuring accuracy |
|
Capacitance |
± (1% of reading+0.5pF) |
Relative Permittivity |
±(1~10)% of reading |
Dielectric dissipation factor |
± (5% of reading+0.0002) |
DC Resistivity |
±10% of reading |
Resolution |
|
Capacitance |
0.01pF |
Relative permittivity |
0.001 |
Dielectric dissipation factor |
0.00001 |
Measured temperature range |
0~120℃ |
Temperature measurement error |
±0.5℃ |
AC Test Voltage |
200~2200V Continuously adjustable, frequency 50Hz |
DC Test Voltage |
0~500V Continuously adjustable |
Power consumption |
100W |
Ambient temperature |
0℃~40℃ |
Relative humidity(RH) |
<75% |
Dimensions |
450mm×410mm×320mm |
Total weight |
25KG |
4. Functions & Features
1). The test cell adopts the three-electrode structure according to national standard GB/T5654-2007, with electrode spacing 2mm, which can eliminate the effects of the stray capacitance and leakage on dielectric loss test results.
2). The instrument adopts the medium frequency induction heating, PID temperature control algorithm. This heating method has the advantages of non-contact between the test cell and the heating body, uniform heating, fast speed, convenient control, and strictly control of the temperature within error range of the preset temperature.
3). Internal standard capacitor is SF6 gas-filled three-electrode capacitance, and its capacitor dielectric loss and electrical capacity are not affected by ambient temperature, humidity etc., so that the instrument accuracy can be ensured even after prolonged use.
4). AC test power supply uses AC-DC-AC conversion, which effectively prevents the fluctuations in mains voltage and frequency from affecting the dielectric loss measurement accuracy. Even use a generator, the instrument can work properly.
5). Perfect protection function. When there is over voltage, over current or high-voltage short circuit, instruments can quickly cut off high voltage, and issues a warning message. When the temperature of the sensor failure or not connected, the instrument will also issue a warning message.
6). There is a temperature limiting relay in the medium frequency induction heating furnace. When temperature above 120 degrees, the instrument frees the relay and stops heating.
7). Convenient test parameter setting. Temperature setting range 0~120℃, AC voltage setting range 200~2200V, DC voltage setting range 0~500V.
8). Using of large TFT touch screen, with backlight and clear display. With simply set up, the instrument can be automatically tested. And automatically store and print test results.
9). Built-in real-time clock, the test date and time can be saved, displayed and printed with the test results.
10). Calibration functions of cleaned dry cell. The measurement of dry cell's capacitance and dielectric loss factor can determine its cleaning and assembly conditions. The calibration data is automatically saved and so that it facilitates the calculation of relative permittivity and DC resistivity.
11). The instrument takes the RAM9 platform as the core, the test accuracy is high and the speed is fast. The whole device is controlled by high-speed single-chip microcomputer, with high automation and easy operation.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. Pre-sale service
1) Communicated through email, phone, WhatsApp, skype, etc., knowing your actual requirements and demands, recommend you the most suitable model.
2) Related technical documents and commercial quotation can be sent within 4 hours.
3) We have many standard models in stock so they can be delivered within short time.
4) OEM and ODM order are accepted, any kind of logo printing or design are available.
5) Good Quality + Factory Price + Quick Response + Reliable Service, is what we are trying best to offer you.
6) All the products are produced by our professional workman and our high-work-effect foreign trade team will solve all your problems from different language, time difference, etc.
Welcome to visit our website and visit our company, welcome your inquiry and contact.
We have many years of R&D and manufacturing experience in the field of 10kv Dielectric Loss Insulation Power Factor Tester Transformer Capacitance & Tan Delta Test Equipment, and can improve the most cost-effective products for you. Whoever has the advantage of talents will have the commanding point of competition. Our company adheres to the development strategy of mutual benefit, sincere cooperation, honesty oriented, and innovation to meet the changes and challenges of the market.
Hot Tags: insulation oil dielectric loss and resistivity tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, transformer oil regeneration system, oil flash point analyzer, oil transfer unit, dielectric strength testing equipment, vacuum pump system, VLF test system