Our Automated Closed Cup flash point tester, no load load tester, SF6 Gas Analyzer and Recovery System is an excellent product that has accumulated experience in manufacturing, widely absorbed user opinions, and has undergone many technical improvements! We will continue to improve and innovate, and continuously enhance our competitiveness and anti-risk ability. We insist on working side by side with customers to help them solve problems and create value for them. We rely on scientific and technological progress to form our own development capability.
1. Application
FTD-6000 Transformer Tan Delta and Capacitance Tester is a new generation test instrument for power industry, which fully automatic on-site measuring dielectric loss (tgδ) and the capacitance (Cx) of electric equipment. It's suitable for testing on transformer, insulating bush, capacitor, CT/PT, MOA etc.
It's also called: Automatic Capacitance and Tan Delta Tester, Capacitance and Dissipation Factor Tester, Capacitance & Dissipation Factor Test Set, Capacitance & Dielectric loss (Tan Delta) measuring bridge, Capacitance & Dissipation Factor Measuring Bridge
2. Dissipation/Power Factor Measurement (Tan Delta) on Instrument Transformers
An insulation failure is often the reason for an instrument transformer (IT) malfunction.
Factors which possibly accelerate the insulation's aging process:
● Moisture ingression due to broken seals
● Heat caused by the ambient temperature or sunlight
Older insulation can lead to high losses in the IT, which generates further heat. Since ITs are not actively cooled, old or degraded insulation can result in a failure or even an explosion. Fragments from the explosion represent a serious hazard for persons in the substation as well as for surrounding equipment.
Dissipation/power factor (tan(δ) delta) measurements help you determine the insulation condition. When using our transformer testing systems, you will also be able to determine the dissipation factor at various frequencies and detect any signs of aging at an early stage. Thus, an IT can be replaced before any further damage occurs.
3. Technical Parameters
Working condition |
-15℃~40℃ |
RH<80% |
|
Anti-interference principle |
Frequency conversion |
||
Power supply |
AC 85V~160V |
Generator can be used |
|
High voltage output |
0.5kV~12kV |
Every 0.1kV |
|
Precision |
2% |
||
Maximum current |
200mA |
||
Capacity |
2000VA |
||
Self-excitation power |
AC 0V~50V/15A |
45HZ/55HZ 47.5HZ/52.5HZ |
|
Resolution |
tgδ: 0.001% |
Cx: 0.001pF |
|
Accuracy |
△tgδ: ±(Reading*1.0%+0.040%) |
||
△Cx: ±(Reading*1.0%+1.00PF) |
|||
Measurement range |
tgδ |
Without limit |
|
Cx |
15pF < Cx < 300nF |
||
12kV |
Cx < 30 nF |
||
5kV |
Cx <150 nF |
||
1kV |
Cx <300 nF |
||
CVT test |
Cx < 300 nF |
||
CVT ratio range |
10~10000 |
||
CVT ratio accuracy |
0.1% |
||
CVT ratio resolution |
0.01 |
||
Storage |
200 group supports U disk data storage |
||
Dimension |
Main unit: 350(L)×270(W)×270(H) |
||
Accessory box: 350(L)×270(W)×160(H) |
|||
Weight |
Main unit: 22.75kg |
||
Accessory box: 5.25kg |
4. Features
1). Adaptive lithium batteries or 220 v ac supply. After a single charge, the dc resistance of hundreds of transformers can be tested continuously. The test process is simple and convenient
2). The output current is six grades, the maximum output current is 10A, the maximum output voltage is 25V, and the current can be automatically selected, which is convenient and fast.
3). Wide range and high accuracy,500uΩ~50KΩ.
4). It has the function of resistance temperature conversion, and can be equipped with wireless temperature measurement module, which can measure the field test temperature in real time to ensure the accuracy of resistance commutation value.
5). It has many kinds of protection functions, such as back EMF protection, broken line protection, power-off protection and over heating alarm.
6). 5.6-inch super industrial high-brightness color LCD screen, still visible under strong sunlight.
7). Equipped with external printer, facilitate data printing
8). It can be stored locally and on USB memory.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. FAQ
Q1. Are you a manufacturer, trading company or a third party? When and where did your factory established?
FUOOTECH: We are a manufacturer established since 2002, located at Chongqing city, China.
Q2: Can you produce your products as our requirements, such as put on our logo?
FUOOTECH: Yes, OEM and ODM are available. We have the professional technical team to design the products as per your request.
Q3. What's the minimum order quantity?
FUOOTECH: 1 Set.
Q4. Will the products be tested before shipping?
FUOOTECH: Yes, of course. QC personal will have a strict testing procedure to all the products before shipping.
We can provide customers with the most satisfactory answers in a short time, and create higher added value for our 12kv Fully Automatic Performed Transformer Capacitance Tan Delta Tester Cdf Transformer Tester. Through long-term practice, our company has accumulated rich technology, management and market experience. Our company has established long-term cooperation relationship with many enterprises with the tenet of 'quality casting brand, good faith service for customers', and in line with the principle of 'customer first and good faith'.
Hot Tags: automatic anti-interference transformer tan delta and capacitance tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, phosphate ester fire resistant hydraulic fluid Purifier, Acidity test value of transformer oil, Oil Dissolved Gas Analyzer, variable frequency dielectric loss tester, Portable Density Tester, Transformer Loss Tester