We are carefully committed to the development and construction of corporate culture, personalized and high-grade transformer oil breakdown voltage tester, flash point tester, Insulation Resistance Tester, so that our company takes a big step forward to a modern type of enterprise. Through a global marketing network, the company provides efficient and convenient products and technical services for electric power, petrochemical, manufacturing, real estate, and other industries. Through systematic scientific analysis of economy, industry, competition, resources and management, our company has made systematic planning and adjustment of corporate strategy and organizational management system. According to the actual needs of the company's development, technological progress and technological transformation, combined with the current situation of the company's human resources, we constantly improve the training and development system, take advantage of existing training resources, and take a variety of effective measures for different positions and different training needs.
1. Application
FUOOTECH’s FTDC-40A Transformer DC Resistance Testing Equipment is designed for testing the DC resistance of inductance circuit such as power transformer coil, current transformer coil and so on.
This winding resistance test set can check the welding quality of the winding joints and whether the winding have inter-turn short circuits. It can test whether the contact of each position of the voltage tap switch is good, whether the actual position of the tap changer matches the indicated position, whether the lead wire is broken, and the multi-stranded wire is wound in parallel. Whether there is stock breakage, etc.
2. About DC Winding Resistance Test
Large power transformers are very valuable and expensive assets that are key to the operation of the electric power system. This includes generator step-up (GSU) transformers that connect generators to the transmission system.
Many of these transformers are approaching or have already exceeded their expected lifespan. According to a U.S. Department of Energy report in 2012, 70 percent of large power transformers on the power system in the United States were over 25 years old, with the overall average transformer age being 40 years.
With aging infrastructure, the routine maintenance and testing of large power transformers has become increasingly necessary to ensure that the equipment remains in good working condition. GSUs are especially important because a failure results in a loss of generation.
One commonly used transformer test is Direct Current (DC) winding resistance testing. Unless the transformer is intentionally demagnetized following this test, significant residual flux remains in the transformer. When the unit is returned to service, the currents and voltages seen during energization can differ from typical values. These changes in current and voltage have the potential to modify the response of generator and transformer protection relays when the unit is energized for the first time following the testing.
3. Technical Parameters
Item | Parameter | Inaccuracy |
Test Current | <20mA、2.5A、5A、10A、20A、40A | |
Test Range | 50μΩ~500mΩ (40A) | accuracy:±(0.2%+2digit) |
10Ω-20KΩ (<20mA) | accuracy:±(0.5%+2digit) | |
Best Resolution | 0.1μΩ | |
Display | LCD | 4 effective digits for resistance value |
Storage | 1000sets | |
Environmental | Operating Temp.:0℃~40℃ | |
Relative Humidity | <90%RH,non-condensing | |
Power Supply | AC 220V±10V, 50Hz±1 Hz | Fuse 5A |
Max Power | 500W | |
Dimension | 400×225×350(mm) | |
Weight | Instrument Box 15.5KG, Wire Box:6KG |
4. Features
1). Download app (Android) to control instrument completely, upload test data for easy reference.
2). 7-inch high resolution LCD touch screen, easy on-site operation. Good visibility under strong light.
3). New power supply technology with multiple current gears and a wide measurement range. The current can be automatically selected according to the load, which is suitable for DC resistance measurement of medium-sized and large transformers and voltage transformers.
4). A complete and reliable protection system, protect instrument from impact of back EMF.
5). Internal data storage up to 1000 sets.
6). RS232 port and USB Port for data storage and PC communication.
7). Built-in high-speed micro printer.
8). With audible discharge alarm, clear discharge instructions.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. FAQ
1). When can I get your technical and commercial offer?
FUOOTECH: We usually quote within 4 hours after we get your inquiry.
If you are very urgent to get price, please call us or tell us in your email so that we will regard your inquiry priority.
2. What about the leading time for production?
FUOOTECH: it depends on the order quantity and the product. Usually our leading time is within 7 working days after order confirmed.
3. What are your price terms?
FUOOTECH: We accept EXW,FOB, CFR, CIF, ect. You can choose the one which is the most convenient and cost effective for you.
4. How much will be the Shipping cost and time?
FUOOTECH: It depends on the size & weight of your goods and the method of shipping (by sea/ by air/by Express) and your designated port or airport. We will be grateful if you can spare us some minutes to evaluate the cost based on the information provided.
Welcome to contact us for any inquiry and cooperation.
The excellent quality of our 20A Winding Resistance Ohmmeter Transformer DC Resistance Measurement Kit Price makes us very confident in the whole competitive market. We are able to ensure fast and efficient solutions for customers. We know that the best way for our employees to make greater achievements is to praise them when they make achievements.
Hot Tags: 40a transformer dc winding resistance meter, China, suppliers, manufacturers, customized, price, in stock, buy discount, Comprehensive Sf6 Gas Analyzer, Hand held transformer winding resistance tester, Digital Surface Tensiometer, transformer oil drying equipment, low resistance meter 50A, oil acidity test kit