sales@fuootech.com    +86 13527390908
Cont

Have any Questions?

+86 13527390908

5A/10A/20A/50A/100A Transformer Winding Resistance Tester Automatic Transformer DC Resistance Tester

5A/10A/20A/50A/100A Transformer Winding Resistance Tester Automatic Transformer DC Resistance Tester

Transformer DC resistance is a must-test item for semi-finished products in finished transformer manufacturing, finished product testing, installation, overhaul, change of tap-changer, handover test and preventive test in the power sector.
Send Inquiry

Product Introduction

We promote the development of the palm oil processing machine, digital high voltage insulation resistance tester, oil purifying machine industry through innovation, continuously improve product quality through user feedback, and reflect corporate value by meeting user needs. We combine our own scientific and humane management system, and have stabilized a dynamic enterprise team. We will always follow the pace of the times and society, adhering to the core values of "pragmatic and enterprising, reform and change, people-oriented, cooperation and win-win", innovative and enterprising. The company always adheres to the concept of "pursuing superior quality and inheriting a long history", and sincerely looks forward to sincere cooperation and common development with new and old customers at home and abroad. Our company has a correct understanding of the brand positioning, avoid entering the positioning error, and correctly and effectively implement the positioning strategy to achieve the success of brand positioning.

1. Introduction & Application

Transformer DC resistance is a must-test item for semi-finished products in finished transformer manufacturing, finished product testing, installation, overhaul, change of tap-changer, handover test and preventive test in the power sector.

It is able to check the welding quality of the winding joint and the presence or absence of the turn-to-turn short circuit of the winding, and it is possible to detect whether the contact of each position of the voltage tap changer is good and whether the actual position of the tap changer and the indicated position are consistent, whether the lead wire is broken, and the multi-strand wire is wound. Whether there are broken shares and so on.

In order to meet the needs of rapid measurement of DC resistance of transformers, FUOOTECH developed FTDC-100A DC resistance tester. The whole machine is controlled by high-speed single-chip microcomputer with high degree of automation and automatic discharge and discharge alarm function. The instrument has high test accuracy and easy operation, and can realize rapid measurement of the direct resistance of the transformer.

More details of 100A Transformer DC Resistance Tester

2. Security Measures

1). Be sure to read this manual carefully before using this instrument.

2). The operator of the instrument should have common knowledge of the use of general electrical equipment or instruments.

3). This instrument can be used indoors and outdoors, but should be used away from rain, corrosive gas and other places.

 

4). The instrument should avoid severe vibration.

5). Maintenance, care and adjustment of the instrument should be carried out by professionals.

6). After the test is completed, be sure to wait for the discharge alarm sound to stop before turning off the power and remove the test line.

 

7). To measure the no-load voltage regulating transformer, be sure to switch the gear position after the discharge indicating alarm sound stops.

8). During the test, it is forbidden to move the test clip and power supply line.

100A Transformer DC Resistance Tester using at site

3. Technical Parameters

1). The output current: 100A, 50A, 20A, 10A, 5A

2). The minimum resolution: 0.1μΩ

3). Range: 100A: 50μΩ~100mΩ, 50A: 100μΩ~200mΩ

20A: 200μΩ~800mΩ, 10A: 500μΩ~2Ω, 5A: 1mΩ~4Ω.

4). Accuracy: ± (0.2% + 2 words)

5). Weight: 15KG without test line

 

4. Precautions

1). It is necessary to wait for the discharge to end. After the alarm sound stops, the line is removed again, otherwise it is dangerous.

 

2). When measuring the unloaded voltage regulating transformer, the discharge must be reset before the reverse tapping, and the switch point can be switched after the alarm sound stops.

 

3). When selecting current, refer to the range in the technical index column. When the current is over-range, the instrument is always in the "charging" state because the current does not reach the preset value. At this time, press the reset button to reset the instrument and re-select the smaller one. Current gear. When the range is under-balanced, "Current current is too small" is displayed. When these two states occur, the range is confirmed and a larger current is selected for testing.

 

4). After the test is completed, press the "Reset" button, the instrument power will be disconnected from the winding, discharge at the same time, the audible alarm, the ammeter will return to the zero position, then the display will return to the initial state, and the discharge can be rewired after the end of the discharge. Take the next measurement or remove the test line and the power cord to end the measurement.

 

5. Stocks at office

100A Transformer DC Resistance Tester in stocks

6. Packing, Delivery, Shipping and Payment

deliver fuootech 100A Transformer DC Winding Resistance Tester

 

7. Certificates

FUOOTECH winding resistance tester certificate

 

8. FAQ

Q1. Are you a manufacturer, trading company or a third party? When and where did your factory established?

FUOOTECH: We are a manufacturer established since 2002, located at Chongqing city, China.

Q2: Can you produce your products as our requirements, such as put on our logo?
FUOOTECH: Yes, OEM and ODM are available. We have the professional technical team to design the products as per your request.

Q3. What's the minimum order quantity?
FUOOTECH: 1 Set.
 

Welcome to contact us for any inquiry and cooperation.

fuootech W.jpg

 

Our company always adheres to technological innovation and scientific development of high-quality service, follows the market development trend, and constantly introduces high-tech and high-quality new 5A/10A/20A/50A/100A Transformer Winding Resistance Tester Automatic Transformer DC Resistance Tester on the basis of independent innovation. The company has strong technical force and complete testing methods, and our product quality has a good reputation abroad. With the innovative spirit of constantly moving forward, we inspire the passion to challenge ourselves, advance with the times, and reach new heights.

Hot Tags: 100a transformer dc winding resistance tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, Transformer oil water content analyzer, Dc Winding Resistance Tester 40A, digital tensiometer, resistivity tester, megohmmeter insulation test meter, fuel oil purifier

Send Inquiry