We pay close attention to the market dynamics of vacuum oil filter, dissolved gas analysis monitor, oil filter cart at home and abroad. According to the feedback from the market and users, we constantly develop and research new products to meet the different needs of customers. While we are actively developing and growing, we have also been actively fulfilling our social responsibilities and actively participating in charitable activities. The company takes high-quality products and strong scientific research as its core competitiveness to build an advanced and excellent enterprise.
1. Application
FTCT-1000A CT/PT Analyzer is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, demagnetization, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopt LCD, built-in printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.
2. Current Transformer (CT)?
A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary.
Current transformers, along with voltage or potential transformers, are instrument transformers. Instrument transformers scale the large values of voltage or current to small, standardized values that are easy to handle for measuring instruments and protective relays. The instrument transformers isolate measurement or protection circuits from the high voltage of the primary system. A current transformer provides a secondary current that is accurately proportional to the current flowing in its primary. The current transformer presents a negligible load to the primary circuit.
Current transformers are the current-sensing units of the power system and are used at generating stations, electrical substations, and in industrial and commercial electric power distribution.
3. Function Table
Current Transformer (CT) |
Voltage Transformer (PT) |
1. Magnetization Curve |
1. Excitation Characteristic Test |
2. Transformation Ratio Test |
2. Transformation Ratio Test |
3. Polarity |
3. Polarity |
4. 5% and 10% error curve |
4. Withstand Test of Power Frequency Alternating Current |
5. Current Injecting |
5. Degauss |
6. Demagnetization |
6. Calculation of Knee Point Value |
7. Withstand Test of Power Frequency Alternating Current |
7. Actual Secondary Load Test |
8. Automatic Calculation of Excitation Knee Point Value |
8. Resistance Test |
9. Actual Secondary Load Test |
|
10. Resistance Test |
4. Technical Parameters
Operational Power Supply |
AC220V±20V, 50~60Hz |
Equipment Power Supply Output Waveform |
Sine Wave |
Single Tester Output Voltage of Excitation Characteristic |
0~2500V |
Excitation Output Current |
0~20 A |
Single machine output current of turns ratio test |
0~1000A |
CT ratio measurement range |
5~25000A/5A(5000A/1A) |
PT ratio measurement range |
1~500kV |
Load Range |
5~1000VA |
Resistance measurement range |
0.1~300Ω |
Error |
≤0.5%(0.2%*Reading+0.3%*Range) |
Operating Temperature |
-10℃~+40℃ |
Relative Humidity |
<90RH% |
Altitude |
≤1000m |
Overall Dimension (Length × Width × Height) |
400 *200 * 260(mm) |
Weight |
≤22 Kg |
5. Features
◆ Support the detection of CT and PT, single machine output voltage 0-2500V, current 0-1000A.
◆ All test items can be completed on a single machine without external auxiliary equipment.
◆ Equipped with micro fast printer, it can print test results directly on site.
◆ Adopt intelligent controller, easy to operate.
◆ Large screen LCD, graphic display interface.
◆ Give CT / Pt (excitation) inflection point value automatically according to regulations.
◆ Automatically give 5% and 10% error curves.
◆ 3000 sets of test data can be saved without loss after power failure.
◆ Support u disk to transfer and store data, which can be read through standard PC, and generate test report.
◆ Small and light ≤ 22kg, very convenient for field test.
6. Stocks at office
7. Packing, Delivery, Shipping and Payment
8. Certificates
8. Our Advantages
1) 19 years experience in developping and manufacturing according to related China and internatinoal standards
2) Choose Higher quality raw material from the demostic and worldwide market
3) Own complete and advanced production facilities
4) Has the strict test procedures on raw materials and products from A to Z.
5) Have passed CE, ISO certificates
6) Longer warranty period for all our products (2 Years)
7) Factory Direct Sale, More competitive price
8) Variety types for selection and OEM & ODM are available
Welcome to contact us for any inquiry and cooperation.
We hope to become a leading Automatic Class 0.02 China High Quality Current Transformer CT Analyzer manufacturer that is respected by the society, trusted by our customers and partners, proud of our employees and with outstanding core competitiveness. The company has professional test equipment for customers to test, and has design and research personnel to provide customers with technical services at any time. In addition, the company also has a complete marketing team and after-sales service system, enabling the company to win a good reputation in the process of continuous growth. We have gradually formed strong talent, technology, and brand competitive advantages.
Hot Tags: 1000a power frequency ct pt analyzer, China, suppliers, manufacturers, customized, price, in stock, buy discount, vacuum oil filter, handheld TTR 3 Phase Transformer Turn Ratio Tester, transformer oil regeneration system, liquid filling machine, Portable dew point tester, Transformer Winding Resistance Tester