sales@fuootech.com    +86 13527390908
Cont

Have any Questions?

+86 13527390908

China Manufacturer Low Voltage Transformer Short-Circuit Impedance Winding Deformation Tester

China Manufacturer Low Voltage Transformer Short-Circuit Impedance Winding Deformation Tester

FT-6000C Transformer Load and No Load Loss Tester produced by FUOOTECH Group is mainly used to test capacity, No-load current, No-load loss, short circuit(load) loss, impedance voltage for transformers.
Send Inquiry

Product Introduction

We have a complete industrial chain, which can guarantee sufficient and stable output of the palm oil recycling machine, palm oil recycling system, Lube oil flushing skid. We have insisted on our production procedure innovation together with the most recent modern day managing method, attracting a sizable quantity of talents within this industry. Our factory adheres to the enterprise spirit of 'focusing on morality, pragmatic and innovative', and constantly strengthens the overall quality of the enterprise, and provides good products and services to all sectors of society. We polish every detail of the product to create a work of art with a calm heart and give the product vitality. Our pursuit is to provide customers with excellent products and technical services.

1. Introduction & Application

FT-6000C Transformer Load and No Load Loss Tester produced by FUOOTECH Group is mainly used to test capacity, No-load current, No-load loss, short circuit(load) loss, impedance voltage for transformers.

 

It is small in volume, light in weight, in high accuracy, with steady property, easy to operation can replace the traditional testers. It is displayed by LCD, operated by menu, with friendly interface, is the first choice for all customers.

control panel of transformer capacity test instrument (2)

2. Function & Features

1) Measure the capacity of various distribution transformers, which is convenient and accurate.

2) Measure transformer No-load current, No-load loss, short circuit voltage and short circuit(load) loss.

3) Automatic range switching is carried out inside the instrument, which allows a wide range of voltage and current measurements and simple wiring.

4) When making three phase transformer No-load and load test, the instrument can automatically judge whether the wiring is correct or not, and display the vector diagram of three-phase voltage and current.

5) Finish load test under 1000kVA below distribution transformer full current for single machine. Finish 3150kVA below distribution transformer load test under 1/3 rated current (Under 1/3 rated current, the instrument can be converted to load loss parameters under rated current.)
 

6) All test results are corrected automatically. The instrument automatic correction as follows, waveform correction, temperature correction, non-rated voltage correction and non-rated current correction. The test results are more accurate.

7) 320*240 high brightness LCD screen, with brightness adjustment. Touch buttons make the operation more convenient.

8) The instrument can preset 40 sets parameters of test objects by users, and these parameters can be deleted and increased at any time according to need, so it is very convenient to use.

9) Real-time clock, recording test date automatically, suitable for storage and management of test results.

10) Built-in panel-type thermal printer, fast print test results.

11) Power down store and browse data (test object settings, measurement results, test time) functions. Store up to 500 groups test results.

12) Allows extended range measurement for external voltage transformer and current transformer. Measure test object of any parameters.

FT-6000C Transformer Load And No Load Loss Tester ait site (2)

3. Technical Parameters

Environment condition

● Temperature: -5℃-40℃

● Relative humidity: <95% (at 25℃)

● Altitude: <2500m

● No vibration, no ultra-strong electromagnetic field

● Power input: AC220V± 10%, 45-55Hz.

 

Measurement range

● Internal source:

Current output: 0-10A

Voltage measurement: 0-10V

 

● Capacity test:

30kVA-2500kVA (for 10kV oil and dry transformers)

50kVA-31500kVA (for 35kV oil transformers)

50kVA-2500kVA (for 20kV dry transformers)

50kVA-2000kVA (for 35kV dry transformers)

 

● Measurement range of No-load and load tes t(need external voltage regulator, prepared by customer)

Voltage: 0-600V, automatic switching range.

Current: 0-100A, automatic switching range

Frequency: 45-65Hz.

 

Testing Accuracy

 

● Voltage: ±0.2%FS at 2-100V; ±0.2% at 100-600V

● Current: ±0.2%FS at 0.5-10A; ±0.2% at 10-100A

● Power: ±0.5% at cosφ>0.1; ±1.0% at 0.02

 

Insulation strength

 

● Insulation resistance of Voltage and current input terminal to shell ≥100MOhm

● Withstand voltage between power supply and shell is 2kV RMS, 1mins.

● Dimension: 400*300*220mm

● Weight: 6kg. (accessories are not included.)

 

4. Stocks at office

transformer capacity test instrument in stocks (2)

5. Packing, Delivery, Shipping and Payment

deliver fuootech transformer capacity test instrument (2)

 

6. Certificates

FUOOTECH transformer short circuit tester certificate

 

7. Our Advantages

1) 19 years experience in developping and manufacturing according to related China

and internatinoal standards

2) Choose Higher quality raw material from the demostic and worldwide market

3) Own complete and advanced production facilities

4) Has the strict test procedures on raw materials and products from A to Z.

5) Have passed CE, ISO certificates

6) Longer warranty period for all our products (2 Years)

7) Factory Direct Sale, More competitive price

8) Variety types for selection and OEM & ODM are available

Welcome to contact us for any inquiry and cooperation.

fuootech W.jpg

 

Our company has established the 'customer-oriented, quality win' quality policy, the pursuit of first-class quality, first-class service to ensure high-quality China Manufacturer Low Voltage Transformer Short-Circuit Impedance Winding Deformation Tester. You may send us emails and contact us directly. We further promote the progress of enterprise management and achieve better economic and social benefits.

Hot Tags: ft-6000c transformer load and no load loss tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, dissolved gas analysis of transformer oil equipment, Digital Transformer DC Resistance Tester, transformer on load loss tester, Transformer Oil Tan Delta Tester, automatic surface tension test equipment, Gas Chromatograph