We have a complete network system and efficient operation and management capabilities, and we have the core competitive advantage of leading the portable dissolved gas analysis equipment, CT Analyzer, insulating oil dielectric strength tester industry. Our company has many years of production experience, which makes our employees more active and passionate. Our company will uphold the consistent rigorous style, develop more high-quality products with a scientific and pragmatic attitude, so as to provide customers with ideal problem-solving solutions and create a better tomorrow with them. Welcome new and old customers to visit and negotiate business, we will continue to work hard to provide you with the best quality products and services.
1. Application
VLF stands for Very Low Frequency. VLF is generally considered to be 0.1 Hz and lower, its major application is for testing solid dielectric cable, transformers, motors, generators, switchgear and other electrical apparatus.
A VLF hipot is just an AC output tester but with an output frequency of 0.1 Hz or lower rather than 50/60Hz. Although the frequency is very low, it is still an alternating current with polarity reversals every half cycle. At 0.1 Hz output, rather than 60Hz, it takes 600 times less current and power to apply an AC voltage to a capacitive load, like a long cable.
2. Hipot Testing using VLF (Very Low Frequency) Technology for Power Cables
VLF hipot and VLF testing is as simple as just an AC hipot on lower frequency output (at 0.1 Hz). The only way to field test high capacitance loads with AC voltage, like cables and motors/generators, is to use a VLF AC hipot. Lower the frequency, Lower will be the current and power needed to test high capacitive loads.
The reason it has not been widely used for more than 4 ~ 5 years is because only in the last 5 ~ 10 years has it been determined that DC voltage testing damages solid dielectric cable and is an ineffective means of determining insulation quality.
The IEEE/EPRI/CEA and other world engineering bodies recommended VLF test level for solid dielectric cable is up to three times (3Vo) line to ground voltage for 15 + minutes. For example, A 15 kV cable system, with line to ground voltage up to 7.2kV, is to be performed at 22kV.
Many utilities companies do nothing in terms of testing their underground cables and let them fail resulting in necessary emergency repairs, long outages, loss of consumption revenue and annoyed customers. VLF is useful tool to remove or repair the faulty part of the cable in planned shutdown to avoid or overcome any unwanted situation.
3. Technical Parameters
Peak voltage: |
80kV |
Output frequency: |
0.1Hz, 0.05Hz and 0.02 Hz (selectable) |
Fuse: |
20A |
Maximum load capacity: |
1.1μF@0.1Hz, 2.2μF@0.05Hz, 5.5μF@0.02Hz |
Measurement accuracy: |
3% |
Voltage positive and negative peak error: |
≤3% |
Voltage waveform distortion: |
≤5%. |
Working environment: |
Temperature: -10ºC ~ +50ºC, 85%RH. |
Indoor or outdoor |
|
Weight: |
Control unit:4kg |
Power supply: |
220V ±10%, 50Hz ±5% |
If using a portable generator, make sure the output voltage and frequency are stable. Power >3kW. |
4. More Technical Data for Various Models
Model |
Rated voltage |
Load capacity |
Fuse |
Weight |
Purpose |
FTAC-VLF-30/1.1 |
30kV |
0.1Hz ≤1.1µF |
10A |
Controller:4kg |
10KV and below voltage |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
|||||
FTAC-VLF-40/1.1 |
40kV |
0.1Hz ≤1.1µF |
10A |
controller:4kg |
13KV and below voltage |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
|||||
FTAC-VLF-50/1.1 |
50kV |
0.1Hz ≤1.1µF |
20A |
Controller:4kg |
15.75KV and below |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
|||||
FTAC-VLF-60/1.1 |
60kV |
0.1Hz ≤1.1µF |
20A |
Controller: 4 kg |
18KVand below voltage |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
|||||
FTAC-VLF-80/1.1 |
80kV (Peak) |
0.1Hz ≤1.1µF |
20A |
Controller: 4 kg |
35KV and below voltage |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
More details on VLF testing 30/40/50/60/70/80/90kV, please contact FUOOTECH, we have professional tech team to design correctly designed products and systems.
5. Functions & Features
1). Adapts microprocessor controlled, can realize voltage set-up/down, measuring and protecting automatically. Manual intervention is allowable even during the auto voltage boosting.
2). Portable, small size and light weight, easy to move. It is very convenient for outdoor operation.
3). Large LCD touch screen can display waveform clearly, and test report can be printed via built-in printer.
4). The data of current, voltage, and waveform can be sampled at HV side.
5). A high voltage output protective resistor is provided in the voltage boost body in the design and this eliminates the need of additional protective resistor connected outside.
6). Closed-loop negative feedback circuit is adopted. No capacity rising during outputting.
7). Over voltage and current protection: When the output is beyond the limitation, the control unit will shut itself down within 20ms.
6. Stocks at office
7. Packing, Delivery, Shipping and Payment
8. Certificates
9. FAQ
Q1. What's the minimum order quantity?
FUOOTECH: 1 Set.
Q2. Will the products be tested before shipping?
FUOOTECH: Yes, of course. QC personal will have a strict testing procedure to all the products before shipping.
Q3. What's your warranty period?
FUOOTECH: We offer 12 months of warranty for all our products from the date of shipment. Even if the warranty period is expired, we still provide lifelong maintenance, technical service and spare parts supply.
Q4. Can we visit your factory before place the order? Is FAT acceptable?
FUOOTECH: Yes, sure. Welcome to visit us to check our company and products at your free time. FAT is acceptable.
Welcome to contact us for your inquiry and order.
Providing customers with high-quality, safe and reliable products is our eternal foothold. We will continue to surpass ourselves and, as always, create higher value for customers and provide better China Supplier High Voltage Generator AC Hipot Tester Vlf Cable Tester and after-sales service. We have professional technical personnel to ensure that the quality of each process meets customer requirements, so that you can rest assured and truly achieve our win-win situation. We always adhere to the implementation of high-quality strategy, "to create high-quality projects, to shape the first-class brand" as a strategic policy.
Hot Tags: FTAC-VLF-80/1.1 80kVAC VLF Hipot Test Set, China, suppliers, manufacturers, customized, price, in stock, buy discount, oil tan delta tester, Transformer Oil Dissolved Gas Analyzer, dissolved gas analysis monitor, dielectric loss tester, fuel oil water separator, transformer oil purifier machine