Over the years, we have been dedicated to the oil transfer unit, Transformer Voltage Ratio Tester, high voltage Insulation Resistance 20kv Tester business, and have won the trust and praise of users with advanced technology, excellent quality, and a win-win strategic cooperation policy. No matter what kind of requirements you have on the equipment, you are welcome to contact us. We have accumulated a wealth of practical experience, reserve a high-quality professional talent team, the performance has attracted the attention of the industry.
1. Introduction & Application
Series FT-706 Automatic Petroleum Oil Acid Value Number Tester can test 6 cups of oil samples. It's designed and manufactured by FUOOTECH Group according to client's actual demand.
Transformer and turbine oil acid number detection is a routine inspection item for power systems and oil-filled electrical equipment in industrial and mining enterprises. A special reagent bottle is used to hold the extraction liquid and the neutralization liquid. The extraction liquid is stored in glass containers to ensure that there are no plastic additive contaminants. The neutralization solution is stored in polyethylene plastic bottles, which completely avoids the possibility of caustic potassium reacting with glass. In addition, the neutralization liquid balance gas and solid purification device completely avoids the influence of carbon dioxide and water vapor on the concentration of the neutralization liquid, and there is no mistake in using high-concentration caustic potassium or caustic soda purification solutions as titration standard solutions.
During the working process, the user does not need to touch the organic solvent by hand, which reduces the harm of chemicals to the human body. According to user needs, FT-706 automatic acid number tester can measure 1 to 6 samples respectively.
2. Advantages of FT-706
This oleic acid value measuring instrument adopts the principle of neutralization method. At normal temperature, microcomputer control automatically completes adding liquid, stirring, titration and terminal point judgment. All working parameters are selected by touch-type liquid crystal screen, the man-machine interface is simple and friendly, easy to operate, and the average analysis cycle of oil sample is about 2 minutes. It can display as many as 35 groups of determination results, and can print out a number of parameters related to the determination.
3. Technical Parameters
Test range |
0.001~ 0.900 mg KOH/g |
Correlation coefficient |
0.999~0.9998 |
Recovery rate |
98 ~103% |
Minimum resolution |
0.001 mg KOH/g |
Repeatability |
2~5% (RSD) |
Accuracy |
± 0.003 mg KOH/g (0.001 ~ 0.100 mg KOH/g) |
Display mode |
large touch-screen color LCD screen |
Dimensions |
(width) 420 mm × (height) 190 mm × (depth) 340 mm |
Net weight |
9kg |
Ambient temperature |
0~40ºC |
Relative humidity |
≤ 85% |
Working power supply |
AC 220V ± 10% |
Power frequency |
50 ± 5 Hz |
Power consumption |
<150 W |
For more details on Oil Acid Value Tester, please contact us, we have professional tech team to design correctly designed products and systems.
4. Functions & Features
1). 6 cups design is suitable for testing the acid value of transformer oil and turbine oil.
2). Single-chip microcomputer improves work efficiency.
3). Automatically completes the operation of extractant addition, neutralization titration and endpoint discrimination, acid value calculation, data storage and printout.
4). The man-machine dialogue interface is simple and friendly, and the operation is convenient.
5). It is not necessary to prepare self-extracting liquid and neutralizing liquid, etc. the average test time of oil sample is about 2 minutes.
6). The resistive touch screen is bright and elegant with accurate input parameters and stable and reliable performance.
7). Power off storage function, which can store the latest 100 test results
8). Up to 35 groups of measurement results can be displayed separately, and a number of measurement-related parameters can be printed out.
9). The automatic calibration function of the standard acid can eliminate the system error and guarantee the accuracy of the determination result.
10). Large capacity and high efficiency carbon dioxide and water purification system ensures the stability of neutralization liquid concentration.
11). The design of the chassis is simple and reasonable, the size is small and exquisite, the appearance is elegant and generous.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. After-sales Service
1). The warranty period is 12 months from commissioning acceptance date on. After the warranty period is over we provide lifelong maintenance and technical service.
2). We guarantee the maintenance time no more than 3 working days and response time within 1 hour.
3). We build instrument service profile for our clients to record the product service and maintenance conditions.
4). After instruments start service, we will pay follow-ups to collect the service conditions.
The superiority of our China Suppliers (0-80KV) Automatic Transformer Insulation Oil Dielectric Strength Test Kit Portable Insulating Oil Breakdown Voltage Bdv Tester Price and the stability of our quality are the keys to solidify our customers. In our business activities, we use legal means to safeguard the legitimate rights and interests of the enterprise itself and correctly handle the law-related affairs in the process of production and operation management such as reform and restructuring of the enterprise, and at the same time, protect the legitimate rights and interests of the employees according to the law. We continue to launch the most cost-effective competitive products, prices and delivery speed, and we also strive to win customer satisfaction.
Hot Tags: 6 cups automatic transformer oil acidity tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, Turns Ratio Tester, insulating oil purifier, palm oil recycling system, fuel oil purification plant, light diesel oil filtration, liquid density meter