We continue to create business value and social value with the best kinematic viscosity testing apparatus, PLC Control oil purification system, megohmmeter insulation test meter and provide full service for our customers. We continue to improve the business management system and provide users with comprehensive pre-sales, sales and after-sales services. With the intensification of competition in the market and various resources, the competition for talents has become increasingly fierce. The whole process of our production, from the purchase of raw materials, incoming inspection, process control, finished product inspection to product delivery, and after-sales service, strictly follow the quality assurance system. Scientific and effective human resource management is the guarantee for the sustainable development of enterprises.
1. Introduction & Application
Transformer DC resistance is a must-test item for semi-finished products in finished transformer manufacturing, finished product testing, installation, overhaul, change of tap-changer, handover test and preventive test in the power sector.
It is able to check the welding quality of the winding joint and the presence or absence of the turn-to-turn short circuit of the winding, and it is possible to detect whether the contact of each position of the voltage tap changer is good and whether the actual position of the tap changer and the indicated position are consistent, whether the lead wire is broken, and the multi-strand wire is wound. Whether there are broken shares and so on.
In order to meet the needs of rapid measurement of DC resistance of transformers, FUOOTECH developed FTDC-100A DC resistance tester. The whole machine is controlled by high-speed single-chip microcomputer with high degree of automation and automatic discharge and discharge alarm function. The instrument has high test accuracy and easy operation, and can realize rapid measurement of the direct resistance of the transformer.
2. Security Measures
1). Be sure to read this manual carefully before using this instrument.
2). The operator of the instrument should have common knowledge of the use of general electrical equipment or instruments.
3). This instrument can be used indoors and outdoors, but should be used away from rain, corrosive gas and other places.
4). The instrument should avoid severe vibration.
5). Maintenance, care and adjustment of the instrument should be carried out by professionals.
6). After the test is completed, be sure to wait for the discharge alarm sound to stop before turning off the power and remove the test line.
7). To measure the no-load voltage regulating transformer, be sure to switch the gear position after the discharge indicating alarm sound stops.
8). During the test, it is forbidden to move the test clip and power supply line.
3. Technical Parameters
1). The output current: 100A, 50A, 20A, 10A, 5A
2). The minimum resolution: 0.1μΩ
3). Range: 100A: 50μΩ~100mΩ, 50A: 100μΩ~200mΩ
20A: 200μΩ~800mΩ, 10A: 500μΩ~2Ω, 5A: 1mΩ~4Ω.
4). Accuracy: ± (0.2% + 2 words)
5). Weight: 15KG without test line
4. Precautions
1). It is necessary to wait for the discharge to end. After the alarm sound stops, the line is removed again, otherwise it is dangerous.
2). When measuring the unloaded voltage regulating transformer, the discharge must be reset before the reverse tapping, and the switch point can be switched after the alarm sound stops.
3). When selecting current, refer to the range in the technical index column. When the current is over-range, the instrument is always in the "charging" state because the current does not reach the preset value. At this time, press the reset button to reset the instrument and re-select the smaller one. Current gear. When the range is under-balanced, "Current current is too small" is displayed. When these two states occur, the range is confirmed and a larger current is selected for testing.
4). After the test is completed, press the "Reset" button, the instrument power will be disconnected from the winding, discharge at the same time, the audible alarm, the ammeter will return to the zero position, then the display will return to the initial state, and the discharge can be rewired after the end of the discharge. Take the next measurement or remove the test line and the power cord to end the measurement.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. FAQ
Q1. Are you a manufacturer, trading company or a third party? When and where did your factory established?
FUOOTECH: We are a manufacturer established since 2002, located at Chongqing city, China.
Q2: Can you produce your products as our requirements, such as put on our logo?
FUOOTECH: Yes, OEM and ODM are available. We have the professional technical team to design the products as per your request.
Q3. What's the minimum order quantity?
FUOOTECH: 1 Set.
Welcome to contact us for any inquiry and cooperation.
We will strengthen the productivity of our products and continuously improve the performance of our products. We hope that through our intentions and changes, we will continue to meet the individual needs of customers for DC Low Resistance Tester with Speed (60 times/sec) Accuracy (0.02%) products and become a good partner worthy of your trust. Our company has a number of excellent professional and technical personnel and marketing personnel with many years of marketing experience. We have introduced a number of German high-precision parts composite machining centers to form key production equipment for parts processing, breaking the foreign technology monopoly, and comprehensively improving the overall process level, manufacturing technology and production capacity.
Hot Tags: 100a transformer dc winding resistance tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, electronic insulation resistance tester, absolute kinematic viscosity bath, portable oil filter machine, digital tensiometer, tan delta test set, oil purification system