Reducing the development time of new transformer short circuit voltage tester, Cleveland Open Flash Point Tester, Power Transformer Vacuum Evacuation machine to the market is the key to our leading edge in the competition. Our company encourages scientific and technological innovation. We have developed frontier in key fields, mastered core technology and owned a number of independent intellectual property rights. We adhere to the tenet of "customer satisfaction is the last word" and sincerely welcome new and old customers at home and abroad to visit and guide!
1. Introduction & Application
Transformer DC resistance is a must-test item for semi-finished products in finished transformer manufacturing, finished product testing, installation, overhaul, change of tap-changer, handover test and preventive test in the power sector.
It is able to check the welding quality of the winding joint and the presence or absence of the turn-to-turn short circuit of the winding, and it is possible to detect whether the contact of each position of the voltage tap changer is good and whether the actual position of the tap changer and the indicated position are consistent, whether the lead wire is broken, and the multi-strand wire is wound. Whether there are broken shares and so on.
In order to meet the needs of rapid measurement of DC resistance of transformers, FUOOTECH developed FTDC-100A DC resistance tester. The whole machine is controlled by high-speed single-chip microcomputer with high degree of automation and automatic discharge and discharge alarm function. The instrument has high test accuracy and easy operation, and can realize rapid measurement of the direct resistance of the transformer.
2. Security Measures
1). Be sure to read this manual carefully before using this instrument.
2). The operator of the instrument should have common knowledge of the use of general electrical equipment or instruments.
3). This instrument can be used indoors and outdoors, but should be used away from rain, corrosive gas and other places.
4). The instrument should avoid severe vibration.
5). Maintenance, care and adjustment of the instrument should be carried out by professionals.
6). After the test is completed, be sure to wait for the discharge alarm sound to stop before turning off the power and remove the test line.
7). To measure the no-load voltage regulating transformer, be sure to switch the gear position after the discharge indicating alarm sound stops.
8). During the test, it is forbidden to move the test clip and power supply line.
3. Technical Parameters
1). The output current: 100A, 50A, 20A, 10A, 5A
2). The minimum resolution: 0.1μΩ
3). Range: 100A: 50μΩ~100mΩ, 50A: 100μΩ~200mΩ
20A: 200μΩ~800mΩ, 10A: 500μΩ~2Ω, 5A: 1mΩ~4Ω.
4). Accuracy: ± (0.2% + 2 words)
5). Weight: 15KG without test line
4. Precautions
1). It is necessary to wait for the discharge to end. After the alarm sound stops, the line is removed again, otherwise it is dangerous.
2). When measuring the unloaded voltage regulating transformer, the discharge must be reset before the reverse tapping, and the switch point can be switched after the alarm sound stops.
3). When selecting current, refer to the range in the technical index column. When the current is over-range, the instrument is always in the "charging" state because the current does not reach the preset value. At this time, press the reset button to reset the instrument and re-select the smaller one. Current gear. When the range is under-balanced, "Current current is too small" is displayed. When these two states occur, the range is confirmed and a larger current is selected for testing.
4). After the test is completed, press the "Reset" button, the instrument power will be disconnected from the winding, discharge at the same time, the audible alarm, the ammeter will return to the zero position, then the display will return to the initial state, and the discharge can be rewired after the end of the discharge. Take the next measurement or remove the test line and the power cord to end the measurement.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. FAQ
Q1. Are you a manufacturer, trading company or a third party? When and where did your factory established?
FUOOTECH: We are a manufacturer established since 2002, located at Chongqing city, China.
Q2: Can you produce your products as our requirements, such as put on our logo?
FUOOTECH: Yes, OEM and ODM are available. We have the professional technical team to design the products as per your request.
Q3. What's the minimum order quantity?
FUOOTECH: 1 Set.
Welcome to contact us for any inquiry and cooperation.
By further strengthening precision technology and applying it to the DC Transformer Resistance Tester, DC Winding Resistance Tester, Power Transformer DC Resistance Tester, our competitiveness continues to increase. The company attaches great importance to and implements the brand building strategy, and continues to provide the company's products with industry influence and technological innovation. We actively seek breakthroughs in market, channel and business model to serve global users.
Hot Tags: 100a transformer dc winding resistance tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, explosion proof oil purifier, lube oil purifier, Gas Chromatograph, Transformer no load load tester, Power Transformer Vacuum Evacuation machine, transformer oil purification