Our portable oil filter, VLF High Voltage Generator, low temperature oil density meter is independently developed and produced, sold directly by the factory, and the price is lower than other brands of the same quality. The spirit of our enterprise includes responsibility, pragmatism, loyalty, tolerance, transcendence and home. Our company is willing to cooperate wholeheartedly with you to create a better future with satisfactory service, advanced technology and equipment, strong technical force, and excellent product quality. Our company has the determination to fundamentally reform the business of traditional enterprises, take the road of joint operation and common development and adhere to the long-term and sustainable development policy.
1. Application
The rapid development of modern industry, the insulation test of high-voltage equipment puts forward higher requirements, and the traditional measurement methods will face severe tests. With the large-scale application practice of optical fiber in intelligent substation, FTIR-10M 10KV insulation resistance tester has good insulation and anti-interference ability, high measurement accuracy, easy miniaturization, and extremely low failure rate, which has received extensive attention. It is widely used to solve the evaluation of electrical insulation quality of large high-voltage transformers, electric motors, generators, long-distance power cables and tubular busbars under high-voltage substation and power plant on-site strong interference.
EPR50C Digital insulation resistance meter consists of medium and large scale integrated circuits. The output power of the watch is large, and the output voltage level is a lot (with 6 voltage levels). Rated insulation test voltage range 250V ~ 10kV, insulation resistance measurement range 0.01MΩ ~ 2000GΩ. DC voltage measurement range 0 ~ 1000V, AC voltage measurement range 0 ~ 750V.
2. Warns before Use This Insulation Resistance Tester?
For safety, before use the instrument must be well earthed, because the measured target connects to high voltage power, and exists power frequency leakage.
Once high voltage has started, do not use manual discharge method to check the instrument. After test, please wait till the instrument completes automatic discharge and automatically returns to zero, then manual discharge can be operated. That is because electrical pulse caused by short-circuit discharge will damage the insulation life of the measured object; if the pulse fleeing into the instrument, will also damage the integrated circuit inside the instrument.
The instrument is designed for HV substations and power plants to test the characteristic of large HV transformer, electric machines and appliances, remote power cable or buried cable and other electrical insulation resistance in strong interference environment. It also can be widely used for testing characteristics of insulation resistance in other area.
3. Technical Parameters
Test Function |
Insulation resistance test, voltage test |
|
Condition |
23°C±5°C,below 75%rh |
|
Rated voltage (V) |
250, 500, 1000, 2500V, 5000V, 10000V |
|
Measuring voltage(V) |
Rated voltage ×(1±10%) |
|
Insulation Resistance Range(GΩ) |
0.01MΩ~2000GΩ, Accuracy: ±3%rdg±5dgt |
|
Insulation Resistance Resolution |
0.01MΩ |
|
DC voltage range |
0~1000V |
Resolution 0.1V |
AC voltage range |
0~750V |
Resolution 0.1V |
Output short circuit current |
≥5mA(10000V) |
|
Absorption Ratio and Polarization Index Measurement |
Have |
|
Power Supply |
12V rechargeable battery |
|
Backlight |
Controllable gray screen backlight, suitable for use in dim places |
|
Display mode |
4-bit large LCD display, gray screen backlight |
|
LCD display size |
108mm×65mm |
|
Instrument size |
227.2mm (L)×227.5mm (W)×153mm (H) |
|
USB interface |
With USB interface, software monitoring, storage data can be uploaded to the computer, save the print |
|
Communication Line |
USB communication line 1PC |
|
Test Line |
High voltage robs red 3meter, high voltage test line black 1.5meter, green 1.5meter |
|
Data Storage |
500 groups, "FULL" symbol indicates that storage is full |
|
Data Review |
Data review function: "READ" symbol display |
|
Overflow Display |
Exceed measurement range overflow function: "OL" symbol display |
|
Alarm Function |
Alarm when the measured value exceeds the alarm setting value |
|
Power Consumption |
Standby: 30mA Max (backlight off) |
|
Turn on backlight: 42mA Max |
||
Measure:300mA Max (backlight off) |
||
Instrument weight |
2720g (including battery) |
|
Battery voltage |
When the battery voltage is low, low battery symbol " " will display |
|
Automatic shut-down |
automatic shutdown after 15 minutes boot |
|
Insulation Resistance |
≥50MΩ (between Measuring line and shell) |
|
Pressure Resistance |
AC3kV/50Hz 1min |
|
Working Temperature and Humidity |
-10℃~+50℃<85%RH |
|
Storage Temperature and Humidity |
-15℃~+55℃<90%RH |
|
Suitable for Safety Regulations |
IEC61010-1, IEC1010-2-31, IEC61557-1,5, IEC60529(IP54), Pollution grade 2, CAT III 300V |
4. Stocks at office
5. Packing, Delivery, Shipping and Payment
6. Certificates
7. FAQ
1). What's the warranty period?
Warranty period is 1 year.
2). What about the leading time for production?
It depends on the order quantity and the product. Usually our leading time is within 7 working days after order confirmed and deposit payment is received.
3). What is your terms of delivery?
EXW, FOB, CFR, CIF all acceptable. You can choose the one which is the most convenient and cost effective for you.
4). How much will be the Shipping cost and time?
This will depend on the size of your goods and the method of shipping (by sea/ by air/by Express) and your designated port or airport. We will be grateful if you can spare us some minutes to evaluate the cost based on the information provided.
Welcome to contact us for your inquiry and order.
We keep building new advantages, creating quality Es3035e 0~2000g Ohm Digital Insulation Resistance Meter Megohmmeter 10kv with our strength and commitment, and allowing superior technology to stand firm in the global market. We vigorously cultivate the innovation system, improve the incentive mechanism, restraint mechanism and fault tolerance mechanism, create an open and inclusive atmosphere, and continuously improve the innovation capability. If you are interested in becoming our partner, you are welcome to contact us for details.
Hot Tags: 10kV High Voltage Insulation Resistance Tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, Transformer DC Winding Resistance Tester, transformer oil purification vacuum degasifier, insulating oil dielectric loss tester, no load current and full load current tester, anti interference transformer dielectric loss tester, Cooking Oil Purifier