We still have a long way to go from the famous brand, we still need to increase our R&D efforts and improve the technical content of our EH oil purification, Transformer vacuum drying System, insulating oil tangent delta tester. We should inherit and carry forward the spirit of indomitable and steel, and make efforts to develop and innovate. We continue to develop new products, improve quality, and provide our customers with good products and perfect services. We have a first-hand source of goods, and we attain obvious advantages in quality and cost performance. We adhere to the prerequisite for the interests of partners and the services of partners to assist partners in common development and common progress.
1. Application
The FTIR-20M High-voltage insulation resistance tester, with 7 range: 500V, 1000V, 2500V, 5000V, 10000V, 15000V, 20000V,test up to 20TΩ, manual voltage regulation function. This insulation resistance tester is designed based on the basic requirements of insulation resistance measurement, using electronic circuits. Its basic principle is to use the voltage and current methods to measure the resistance value of the measured object: R=V/I. The storage and operation circuit make this machine automatically measure the absorption ratio (R1min/R15s) and polarization index (R10min/R1min).
By testing the insulation resistance of different components in the system (transformer, switchgear, wire, motor), the faulty component can be isolated and repaired. Insulation test is used to check the insulation of the test product to ground or between adjacent conductors, which is of great significance to ensure product quality and safety of personnel and equipment in operation. Before powering on the system, use insulation tests to verify that it is sound and can improve the performance of the system; insulation tests can find manufacturing process problems and equipment defects, which are generally not found before the equipment fails. In the European Union, this test is mandatory, even for civil systems.
2. How Insulation Resistance is Measured?
It's well known that good insulation has high resistance; poor insulation, relatively low resistance. The actual resistance values can be higher or lower, depending upon such factors as the temperature or moisture content of the insulation (resistance decreases in temperature or moisture). With a little record-keeping and common sense, however, you can get a good picture of the insulation condition from values that are only relative.
The FTIR-20M insulation tester is a small, portable instrument that gives you a direct reading of insulation resistance in ohms or megohms. For good insulation, the resistance usually reads in the megohm range.
The FTIR-20M electrical insulation resistance tester is essentially a high-range resistance meter (ohmmeter) with a built-in direct-current generator. This meter is of special construction with both current and voltage coils, enabling true ohms to be read directly, independent of the actual voltage applied. This method is nondestructive; that is, it does not cause deterioration of the insulation.
3. Technical Parameters
Accuracy/ Range |
500V |
1000V |
2500V |
5000V |
10000V |
15000V |
20000V |
Unspecified |
<1M |
<1M |
<1M |
<1M |
<1M |
<1M |
<1M |
5% |
1M -10G |
1M -20G |
1M -100G |
1M -100G |
1M -200G |
1M -300G |
1M -400G |
20% |
10G -100G |
20G-200G |
100G-1T |
100G-1T |
200G-2T |
300G -3T |
400G-4T |
Unspecified |
> 100G |
> 200G |
> 1T |
> 1T |
> 2T |
> 3T |
> 4T |
4. Functions & Featuress
1). Strict accordance with the safety standards for design
2). Insulation resistance range 20TΩ @ 20 kv
3). Short circuit current can be adjusted, maximum 5mA (Can be ordered as high as 10mA, short circuit current products).
4). Automatic display polarization index (PI), induced electric absorption test values than (DAR), and can test the leakage current and capacitance.
5). Anti-jamming performance is superior, the interference current reaches 2 mA, still ensure accuracy of test instruments.
6). 2 methods for power: use of lithium ion batteries, battery life can be up to 4 hours (10000V @ 100MΩ).
7). Insulation resistance simulation column.
8). Digital filtering functions, external influence deviation display value causing mitigation point using filter function.
9). Perfect protection function, and the spare fuse prompt functions.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. Accessories
No. |
Item |
Qty |
1 |
Main engine |
1 |
2 |
Power line |
1 |
3 |
Red test line |
1 |
4 |
Black test line |
1 |
5 |
Green test line |
1 |
6 |
Red high voltage shielded wire |
1 |
Welcome to contact us for your inquiry and order.
'Customer initially, High-quality first' in mind, we work closely with our prospects and supply them with efficient and specialist companies for GM-20kv Digital Insulation Resistance Tester Meter Megohmmeter Megger Voltmeter 20kv. All of our employees vigorously inherit and carry forward the spirit of enterprise, forming a strong positive energy to promote the continuous innovation and development of the enterprise. Relying on excellent product quality, good reputation and superior transportation conditions, our company has established a nationwide and worldwide marketing network.
Hot Tags: portable 20kv insulation resistance tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, CT voltage current characteristic integrated tester, oil water separator, 0 1Hz Ultra low frequency high voltage generator, Digital Transformer DC Resistance Tester, transformer evacuation machine, oil regeneration device