We are one of the companies with large operation scale, high processing level and strong comprehensive strength in this insulating oil acidity test kit, 40A Transformer DC Resistance Tester, transformer No load and load loss tester industry. Only by meticulous treatment of each link of production can we ensure that our products are more excellent. Our company always aim to provide the customer best products with lowest price.
1. Introduction and Application
Series ZYD-U Ultra High Voltage Vacuum Transformer Oil Treatment Equipment developed by FUOOTECH Group in 2006 is specially designed for the filtration, dehydration and degasification of the insulating oils including transformer oils, polybutene and silicone fluids in the ultra high voltage electrical equipments.
Ultra High Voltage (UHV) Grid is named as "Electrical High Way" which features big capacity, long distance and low loss. There are 500kV AC, 750kV AC, 1000kV AC, ±660kv DC, ±880kV DC, etc… Considering ensuring its ultra high safety, it has extremely requirements on insulating oils using in the transformer, mutual inductor, and reactor.
Series ZYD-U extra high voltage (EHV) transformer oil purification machine is very powerful in abilities of vacuum degassing, dehydration and filtration for insulating oil or transformer oil. It applies to on-site transformer maintenance and deep purification of new transformer oil, imported transformer oil oil, mutual inductor oil and ultra high voltage transformer oil. It can also be used for transformer oil vacuum filling and vacuum drying operation.
2. Main Functions and Performance
1) Fast vacuum dehydration, degassing and particles removal
2) Suitable for construction, installation, maintenance and on-site inspection of large power transmission and transformation equipment.
3) Used for the deep purification of oil products from capacitors, transformers, and ultra-high voltage transformers.
4) Used for the deep dehydration treatment of oil products that require very low moisture content such as refrigerating oil for air-conditioning compressors.
5) Has the function of oil filling and replenishing for the transformer.
6) Used for oil circulation and drying of transformers.
7) Avaible to proceed vacuum pumping and vacuum oil injecting for the transformer.
8) Due to the dual-stage high-vacuum design, it is more advantageous to use at high-altitude areas.
3. Technical Parameters
Parameters |
Model/ Unit |
ZYD-U-100 |
ZYD-U-150 |
ZYD-U-200 |
ZYD-U-300 |
Flow Rate |
L/H |
6000 |
9000 |
12000 |
18000 |
Ultimate Vacuum Degree |
Pa |
≤ 5 |
|||
Working Vacuum Degree |
Pa |
≤ 30 |
|||
Working Discharge Pressure |
MPa |
≤ 0.5 |
|||
Temperature Control Range |
℃ |
20 ~ 80 |
|||
Operation Temperature |
℃ |
40 ~ 65 |
|||
Power Supply |
|
380V, 50Hz, 3 phases (or as per your requirements) |
|||
Ambient Temperature |
|
-25 ~ 55℃ |
|||
Working Noise |
dB(A) |
65 ~ 90 |
|||
Heating Power (adjusted available) |
KW |
66 |
90 |
132 |
180 |
Total Power |
KW |
72 |
105 |
150 |
200 |
Inlet/Outlet |
mm |
Φ32 |
Φ40 |
φ50 |
φ65 |
Weight |
Kg |
1200 |
1600 |
2200 |
3000 |
Dimension |
mm |
2200×1700×2450 |
2500×1950×2500 |
2850×2050×2600 |
3600×2500×3100 |
Oil Result after Filtration |
Moisture (Water Content) ≤ 3 PPM |
||||
Gas Content ≤0.01% (Vol) |
|||||
Impurities Degree (Filtration precision) ≤ 0.5 micron (no free carbon) |
|||||
Breakdown Voltage (Dielectric Strength) ≥75 KV |
|||||
Flash Point ≥145℃ |
|||||
Granularity 5 ~ 50μm (in 100ml oil sample) ≤ 500 Nos |
|||||
Cleanliness ≤NAS 1638 Grade 6 |
Note: 1. The dimension and weight will be changed with changing of technical specs.
2. All the specs can be customized according to client's requirements.
4. Features
1). Available in different capacities: 3,000 - 30,000 LPH.
2). Works as ultra high vacuum dehydration.
3). UK G technology is adopted to remove trace water, dissolved water effectively and thoroughly.
4). Filter rated up to 1 microns prevents particles from entering back into the transformer. Achieves better than NAS-6.
5). Maintains dissolved gases level, acidity level, TAN Delta, specific resistance, resistivity.
6). Adopt interlocked protective system, which connect oil pump, heater and liquid level sensor, avoiding blank heating, blank pumping, oil leak and electricity leak. If there is any fault, machine will be power off automatically.
7). Online moisture PPM sensor (optional).
8). Mounted BDV test kit (optional).
9). Full laboratory option.
10). Commissioning and FAT on location optionally.
11). PLC making the whole operation automatically as optional.
5. Our Main Customers and Partners
6. Packing, Delivery, Shipping and Payment
7. Onsite Projects
8. Certificates
10. After-Sales Service
* Two (2) years guarantee for product quality. (People damaged parts are charged).
* Lifelong maintenance and spare parts supply.
* Free design of fixtures as customers required.
* Free training for machines installation and operation of the staffs at factory.
* Chargable commissioning and training at client's working site
With excellent leading technology and perfect and reliable product quality, we are providing overall solutions for the Go-Cart Light Oil Recycling Plant, Fuel Oil Coalescence-Separation Oil Purifier industry in all aspects. The company takes "leading the modern home lifestyle" as its mission, and "builds an excellent management enterprise in China, and creates a world-class home furnishing brand" as its corporate vision. After years of hard work, it has now developed into a collection of R&D, production, and sales. , Service-integrated large modern furniture enterprise group Facing the future, we will continue to make progress and develop together with friends from all walks of life. We sincerely look forward to getting more friends' care and support.
Hot Tags: ultra-high voltage vacuum transformer oil treatment plant, China, suppliers, manufacturers, customized, price, in stock, buy discount, Interfacial Tension Test equipment, ttr test equipment, Kinematic Viscosity Apparatus, transformer winding resistance testing equipment, oil tan delta and resistivity tester, high voltage cable hipot tester