To be able to give you benefit and enlarge our business, we also have inspectors in QC Team and assure you our greatest service and products for oil flushing system, handheld TTR 3 Phase Transformer Turn Ratio Tester, 15kv digital insulation resistance tester. As an enterprise, we should have a sense of social responsibility and enthusiastically participate in public welfare. We will provide customers with satisfactory products and services and pour our efforts and exquisite technology with the action policy of "continuous self innovation and always moving forward". We constantly improve the company's production plan management level, shorten the product cycle and improve the company's efficiency. We will further strengthen corporate management, deepen internal reforms, give full play to group advantages, and continue to introduce advanced management concepts.
1. Application
VLF stands for Very Low Frequency. VLF is generally considered to be 0.1 Hz and lower, its major application is for testing solid dielectric cable, transformers, motors, generators, switchgear and other electrical apparatus.
A VLF hipot is just an AC output tester but with an output frequency of 0.1 Hz or lower rather than 50/60Hz. Although the frequency is very low, it is still an alternating current with polarity reversals every half cycle. At 0.1 Hz output, rather than 60Hz, it takes 600 times less current and power to apply an AC voltage to a capacitive load, like a long cable.
2. Hipot Testing using VLF (Very Low Frequency) Technology for Power Cables
VLF hipot and VLF testing is as simple as just an AC hipot on lower frequency output (at 0.1 Hz). The only way to field test high capacitance loads with AC voltage, like cables and motors/generators, is to use a VLF AC hipot. Lower the frequency, Lower will be the current and power needed to test high capacitive loads.
The reason it has not been widely used for more than 4 ~ 5 years is because only in the last 5 ~ 10 years has it been determined that DC voltage testing damages solid dielectric cable and is an ineffective means of determining insulation quality.
The IEEE/EPRI/CEA and other world engineering bodies recommended VLF test level for solid dielectric cable is up to three times (3Vo) line to ground voltage for 15 + minutes. For example, A 15 kV cable system, with line to ground voltage up to 7.2kV, is to be performed at 22kV.
Many utilities companies do nothing in terms of testing their underground cables and let them fail resulting in necessary emergency repairs, long outages, loss of consumption revenue and annoyed customers. VLF is useful tool to remove or repair the faulty part of the cable in planned shutdown to avoid or overcome any unwanted situation.
3. Technical Parameters
Peak voltage: |
80kV |
Output frequency: |
0.1Hz, 0.05Hz and 0.02 Hz (selectable) |
Fuse: |
20A |
Maximum load capacity: |
1.1μF@0.1Hz, 2.2μF@0.05Hz, 5.5μF@0.02Hz |
Measurement accuracy: |
3% |
Voltage positive and negative peak error: |
≤3% |
Voltage waveform distortion: |
≤5%. |
Working environment: |
Temperature: -10ºC ~ +50ºC, 85%RH. |
Indoor or outdoor |
|
Weight: |
Control unit:4kg |
Power supply: |
220V ±10%, 50Hz ±5% |
If using a portable generator, make sure the output voltage and frequency are stable. Power >3kW. |
4. More Technical Data for Various Models
Model |
Rated voltage |
Load capacity |
Fuse |
Weight |
Purpose |
FTAC-VLF-30/1.1 |
30kV |
0.1Hz ≤1.1µF |
10A |
Controller:4kg |
10KV and below voltage |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
|||||
FTAC-VLF-40/1.1 |
40kV |
0.1Hz ≤1.1µF |
10A |
controller:4kg |
13KV and below voltage |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
|||||
FTAC-VLF-50/1.1 |
50kV |
0.1Hz ≤1.1µF |
20A |
Controller:4kg |
15.75KV and below |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
|||||
FTAC-VLF-60/1.1 |
60kV |
0.1Hz ≤1.1µF |
20A |
Controller: 4 kg |
18KVand below voltage |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
|||||
FTAC-VLF-80/1.1 |
80kV (Peak) |
0.1Hz ≤1.1µF |
20A |
Controller: 4 kg |
35KV and below voltage |
0.05Hz ≤2.2µF |
|||||
0.02Hz ≤5.5µF |
More details on VLF testing 30/40/50/60/70/80/90kV, please contact FUOOTECH, we have professional tech team to design correctly designed products and systems.
5. Functions & Features
1). Adapts microprocessor controlled, can realize voltage set-up/down, measuring and protecting automatically. Manual intervention is allowable even during the auto voltage boosting.
2). Portable, small size and light weight, easy to move. It is very convenient for outdoor operation.
3). Large LCD touch screen can display waveform clearly, and test report can be printed via built-in printer.
4). The data of current, voltage, and waveform can be sampled at HV side.
5). A high voltage output protective resistor is provided in the voltage boost body in the design and this eliminates the need of additional protective resistor connected outside.
6). Closed-loop negative feedback circuit is adopted. No capacity rising during outputting.
7). Over voltage and current protection: When the output is beyond the limitation, the control unit will shut itself down within 20ms.
6. Stocks at office
7. Packing, Delivery, Shipping and Payment
8. Certificates
9. FAQ
Q1. What's the minimum order quantity?
FUOOTECH: 1 Set.
Q2. Will the products be tested before shipping?
FUOOTECH: Yes, of course. QC personal will have a strict testing procedure to all the products before shipping.
Q3. What's your warranty period?
FUOOTECH: We offer 12 months of warranty for all our products from the date of shipment. Even if the warranty period is expired, we still provide lifelong maintenance, technical service and spare parts supply.
Q4. Can we visit your factory before place the order? Is FAT acceptable?
FUOOTECH: Yes, sure. Welcome to visit us to check our company and products at your free time. FAT is acceptable.
Welcome to contact us for your inquiry and order.
We improve the management level, and constantly develop new Hzvlf Ultra Low Frequency AC High Voltage Generator 0.1Hz Vlf Hipot Test Set with new advanced technology to gradually expand domestic and foreign markets. We insist on the concept that talent is the first resource of the enterprise and people-oriented, and insist on implementing the policy of respecting labor, knowledge, talent and creation. Our complete quality assurance system can effectively regulate and improve the overall quality of products. Our company is committed to introducing the latest and best technologies and products, as well as the most complete services to the market.
Hot Tags: FTAC-VLF-80/1.1 80kVAC VLF Hipot Test Set, China, suppliers, manufacturers, customized, price, in stock, buy discount, transformer oil dielectric tester, SF6 Gas Analyzer and Recovery System, Oil centrifuge Machine, insulating oil tangent delta tester, tan delta test kit for transformer oil, oil flash point tester