We have never forgotten to strengthen product quality management, and the transformer oil regeneration plant, high vacuum oil water separation, Current Transformer and Potential Transformer Analyzer produced have passed quality certification and comply with environmental protection requirements. The company will consolidate the traditional industry, continue to pursue, forge ahead, and strive to promote the healthy, sustained and steady development of the enterprise. Our corporate vision is the direction of the flag that leads us to unite and advance, and the power of belief that inspires all employees to pioneer and innovate.
1. Application
FTD-6000 Transformer Tan Delta and Capacitance Tester is a new generation test instrument for power industry, which fully automatic on-site measuring dielectric loss (tgδ) and the capacitance (Cx) of electric equipment. It's suitable for testing on transformer, insulating bush, capacitor, CT/PT, MOA etc.
It's also called: Automatic Capacitance and Tan Delta Tester, Capacitance and Dissipation Factor Tester, Capacitance & Dissipation Factor Test Set, Capacitance & Dielectric loss (Tan Delta) measuring bridge, Capacitance & Dissipation Factor Measuring Bridge
2. Dissipation/Power Factor Measurement (Tan Delta) on Instrument Transformers
An insulation failure is often the reason for an instrument transformer (IT) malfunction.
Factors which possibly accelerate the insulation's aging process:
● Moisture ingression due to broken seals
● Heat caused by the ambient temperature or sunlight
Older insulation can lead to high losses in the IT, which generates further heat. Since ITs are not actively cooled, old or degraded insulation can result in a failure or even an explosion. Fragments from the explosion represent a serious hazard for persons in the substation as well as for surrounding equipment.
Dissipation/power factor (tan(δ) delta) measurements help you determine the insulation condition. When using our transformer testing systems, you will also be able to determine the dissipation factor at various frequencies and detect any signs of aging at an early stage. Thus, an IT can be replaced before any further damage occurs.
3. Technical Parameters
Working condition |
-15℃~40℃ |
RH<80% |
|
Anti-interference principle |
Frequency conversion |
||
Power supply |
AC 85V~160V |
Generator can be used |
|
High voltage output |
0.5kV~12kV |
Every 0.1kV |
|
Precision |
2% |
||
Maximum current |
200mA |
||
Capacity |
2000VA |
||
Self-excitation power |
AC 0V~50V/15A |
45HZ/55HZ 47.5HZ/52.5HZ |
|
Resolution |
tgδ: 0.001% |
Cx: 0.001pF |
|
Accuracy |
△tgδ: ±(Reading*1.0%+0.040%) |
||
△Cx: ±(Reading*1.0%+1.00PF) |
|||
Measurement range |
tgδ |
Without limit |
|
Cx |
15pF < Cx < 300nF |
||
12kV |
Cx < 30 nF |
||
5kV |
Cx <150 nF |
||
1kV |
Cx <300 nF |
||
CVT test |
Cx < 300 nF |
||
CVT ratio range |
10~10000 |
||
CVT ratio accuracy |
0.1% |
||
CVT ratio resolution |
0.01 |
||
Storage |
200 group supports U disk data storage |
||
Dimension |
Main unit: 350(L)×270(W)×270(H) |
||
Accessory box: 350(L)×270(W)×160(H) |
|||
Weight |
Main unit: 22.75kg |
||
Accessory box: 5.25kg |
4. Features
1). Adaptive lithium batteries or 220 v ac supply. After a single charge, the dc resistance of hundreds of transformers can be tested continuously. The test process is simple and convenient
2). The output current is six grades, the maximum output current is 10A, the maximum output voltage is 25V, and the current can be automatically selected, which is convenient and fast.
3). Wide range and high accuracy,500uΩ~50KΩ.
4). It has the function of resistance temperature conversion, and can be equipped with wireless temperature measurement module, which can measure the field test temperature in real time to ensure the accuracy of resistance commutation value.
5). It has many kinds of protection functions, such as back EMF protection, broken line protection, power-off protection and over heating alarm.
6). 5.6-inch super industrial high-brightness color LCD screen, still visible under strong sunlight.
7). Equipped with external printer, facilitate data printing
8). It can be stored locally and on USB memory.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. FAQ
Q1. Are you a manufacturer, trading company or a third party? When and where did your factory established?
FUOOTECH: We are a manufacturer established since 2002, located at Chongqing city, China.
Q2: Can you produce your products as our requirements, such as put on our logo?
FUOOTECH: Yes, OEM and ODM are available. We have the professional technical team to design the products as per your request.
Q3. What's the minimum order quantity?
FUOOTECH: 1 Set.
Q4. Will the products be tested before shipping?
FUOOTECH: Yes, of course. QC personal will have a strict testing procedure to all the products before shipping.
We firmly believe that this Probador Tangente De Delta Transformador Tan Delta Automatic Transformer Dielectric Loss Tester industry is full of potential and infinite possibilities in the face of challenges. We constantly improve our corporate image, improve the quality of our employees and enhance our competitive advantage. In response to the complex and severe domestic and international economic situation, we carry forward the spirit of hard work and innovation.
Hot Tags: automatic anti-interference transformer tan delta and capacitance tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, light diesel oil filtration, features comprehensive tester, Oltc Oil Cleaner, oil flash point analyzer, oil dielectric loss tester, Transformer dc resistance test instrument