Three Phase DC Power Transformer Winding Resistance Tester/ 10A DC Resistance Analyzer

FUOOTECH’s FTDC-40A Transformer DC Resistance Testing Equipment is designed for testing the DC resistance of inductance circuit such as power transformer coil, current transformer coil and so on.
Send Inquiry

Product Introduction

With the long-term efforts of all colleagues, our company has a place in the oil water purifier, transformer oil acidity meter, Transformer Loss Tester industry and is developing rapidly on a steady path. Natural selection, survival of the fittest, in the era of fierce global competition, facing the repeated impact of "foreign brands", if traditional enterprises want to stand out in the industry, they must insist on taking sincerity as the center and ingenuity as the quality for sustainability. development of! Our company is equipped with a group of motivated, responsible, capable and united employees.

1. Application

FUOOTECH’s FTDC-40A Transformer DC Resistance Testing Equipment is designed for testing the DC resistance of inductance circuit such as power transformer coil, current transformer coil and so on.

This winding resistance test set can check the welding quality of the winding joints and whether the winding have inter-turn short circuits. It can test whether the contact of each position of the voltage tap switch is good, whether the actual position of the tap changer matches the indicated position, whether the lead wire is broken, and the multi-stranded wire is wound in parallel. Whether there is stock breakage, etc.

FUOOTECH Dc Winding Resistance Tester 40A


2. About DC Winding Resistance Test

Large power transformers are very valuable and expensive assets that are key to the operation of the electric power system. This includes generator step-up (GSU) transformers that connect generators to the transmission system.

Many of these transformers are approaching or have already exceeded their expected lifespan. According to a U.S. Department of Energy report in 2012, 70 percent of large power transformers on the power system in the United States were over 25 years old, with the overall average transformer age being 40 years.

With aging infrastructure, the routine maintenance and testing of large power transformers has become increasingly necessary to ensure that the equipment remains in good working condition. GSUs are especially important because a failure results in a loss of generation.

One commonly used transformer test is Direct Current (DC) winding resistance testing. Unless the transformer is intentionally demagnetized following this test, significant residual flux remains in the transformer. When the unit is returned to service, the currents and voltages seen during energization can differ from typical values. These changes in current and voltage have the potential to modify the response of generator and transformer protection relays when the unit is energized for the first time following the testing.

50A Transformer DC Resistance Tester working at site

3. Technical Parameters

Item

Parameter

Inaccuracy

Test Current

<20mA、2.5A、5A、10A、20A、40A




Test Range

50μΩ~500mΩ (40A)
100μΩ~1Ω (20A)
500μΩ~2Ω (10A)
1mΩ~4Ω (5A)
2mΩ~8Ω (2.5A)


accuracy:±(0.2%+2digit)

10Ω-20KΩ (<20mA)

accuracy:±(0.5%+2digit)

Best Resolution

0.1μΩ


Display

LCD

4 effective digits for resistance value

Storage

1000sets


Environmental

Operating Temp.:0℃~40℃


Relative Humidity

<90%RH,non-condensing


Power Supply

AC 220V±10V, 50Hz±1 Hz

Fuse 5A

Max Power

500W

Dimension

400×225×350(mm)


Weight

Instrument Box 15.5KG, Wire Box:6KG


4. Features

1). Download app (Android) to control instrument completely, upload test data for easy reference.

2). 7-inch high resolution LCD touch screen, easy on-site operation. Good visibility under strong light.

3). New power supply technology with multiple current gears and a wide measurement range. The current can be automatically selected according to the load, which is suitable for DC resistance measurement of medium-sized and large transformers and voltage transformers.

4). A complete and reliable protection system, protect instrument from impact of back EMF.

5). Internal data storage up to 1000 sets.

6). RS232 port and USB Port for data storage and PC communication.

7). Built-in high-speed micro printer.

8). With audible discharge alarm, clear discharge instructions.


5. Stocks at office

40A Transformer DC Resistance Tester in stocks (2)


6. Packing, Delivery, Shipping and Payment

deliver fuootech 100A Transformer DC Winding Resistance Tester


7. Certificates

FUOOTECH winding resistance tester certificate_


8. FAQ

1). When can I get your technical and commercial offer?

FUOOTECH: We usually quote within 4 hours after we get your inquiry.

If you are very urgent to get price, please call us or tell us in your email so that we will regard your inquiry priority.


2. What about the leading time for production?

FUOOTECH: it depends on the order quantity and the product. Usually our leading time is within 7 working days after order confirmed.


3. What are your price terms?

FUOOTECH: We accept EXW,FOB, CFR, CIF, ect. You can choose the one which is the most convenient and cost effective for you.


4. How much will be the Shipping cost and time?

FUOOTECH: It depends on the size & weight of your goods and the method of shipping (by sea/ by air/by Express) and your designated port or airport. We will be grateful if you can spare us some minutes to evaluate the cost based on the information provided.

Welcome to contact us for any inquiry and cooperation.

Our factory


In order to continue to enhance our Three Phase DC Power Transformer Winding Resistance Tester/ 10A DC Resistance Analyzer and deliver more cutting-edge features and performance, we are applying some of the latest improvements in technology. It has been proven that actively assuming social responsibility is conducive to establishing a good image and long-term development of the company. Scientific master production planning plays an important role in controlling product inventory, improving product delivery satisfaction rate, shortening product supply cycle and improving enterprise productivity.

Hot Tags: 40a transformer dc winding resistance meter, China, suppliers, manufacturers, customized, price, in stock, buy discount, Transformer Oil Interfacial Tension Tester, 5A Transformer DC Resistance Tester, karl fischer transformer oil water content testing equipment, 15kv digital insulation resistance tester, handheld TTR 3 Phase Transformer Turn Ratio Tester, oil water purifier