sales@fuootech.com    +86 13527390908
Cont

Have any Questions?

+86 13527390908

Transformer Capacitance Dissipation Insulation Power Factor Tan Delta Test Set

Transformer Capacitance Dissipation Insulation Power Factor Tan Delta Test Set

FTD-9000 Automatic Transformer Dissipation Factor and Capacitance Tester can effectively find the overall damp, deterioration and partly defects of electrical equipment insulation, which are widely used in electrical manufacturing, electrical equipment installation, handover and preventive testing.
Send Inquiry

Product Introduction

We believe that a product design that is positioned precisely in line with consumer psychology will make our Vacuum Pumping and Drying System, Transformer Oil Trace Moiscture Tester, empty load noload loss tester stands out from the crowd of competing brands. We are in line with the 'product is the best spokesperson' the purpose of serving customers, adhering to the 'professional, large-scale, international' development direction and has been the care and love of people from all walks of life. We seek development by reputation and survival by service. Since the establishment of the company, after more than ten years of hard work and hard work, it has continued to grow and develop. We actively promote industrial transformation and upgrading to achieve faster and better development of the enterprise.

1. Application
FTD-9000 Automatic Transformer Dissipation Factor and Capacitance Tester can effectively find the overall damp, deterioration and partly defects of electrical equipment insulation, which are widely used in electrical manufacturing, electrical equipment installation, handover and preventive testing.


The Anti-interference Transformer Dielectric Loss Tester is used for on-site anti-interference, dielectric loss measurement or laboratory dielectric loss measurement. This test instrument is an integrated structure with built-in dielectric loss bridge, variable variable frequency power supply, test transformer and standard capacitor, etc.. The instrument adopts frequency conversion anti-interference and Fourier transform digital filtering technology, fully automatic and intelligent measurement, and the measurement data is very stable under strong interference. The result of measurement is displayed by large screen display, and the instrument comes with micro printer to print and print test results.

accessories of tan delta test of transformer (2)

2. What are the Precautions to be taken before carrying out the Transformer Tan Delta Test?

1) The test set is a source of high voltage electrical energy and operator must use all practical safely precautions to prevent contact with energized parts of the test equipment and related circuits.

2) Never connect the test set to energized equipment.

3) The ground cable must be connected first and removed last.

4) The ground terminal of the input supply card (green lead) must be connected to the protective ground (earth) terminal of the line power source.

5) Keep the high voltage plugs free from moisture, dust during installation and operation.

6) Adequate clearance (Min 1 foot i.e. 30 cm) arc maintained between energized conductor and ground to prevent any arc over.

7) It should be ensured that test specimen is de-energized and grounded before making any further connection and no person may come in contact with HV output terminal or any materiel energized by the output.

8) Porcelain of the bushings shall be clean and dry. Remove any dirt or oil with clean dry cloth.

9) Test shall not be carried out when there is condensation on the porcelain. Preferably, tests shall not be carried out when the relative humidity is in excess of 75%.

tan delta test set at site

3. Technical Parameters

Accuracy

Cx: ±(reading×1%+1pF)
Tgδ: ±(reading×1%+0.00040)

Anti-interference

Variable frequency anti-interference,

the above accuracy can be reached even under 200% interference.

Capacitance range

Internal HV: 3pF~60000pF/12kV 60pF~1.2μF/0.5kV
External HV: 3pF~1.5μF/12kV 60pF~30μF/0.5kV
Best Resolution: 0.001pF, 4 valid digits.

tgδ range

Unlimited, 0.001% resolution, automatic identification for capacitance, inductance and resistance of three tested articles.

Test current range

10μA~1A

Internal HV

Set voltage range: 0.5~10kV/12kV
Maximum output current: 200mA
Buck-boost method: continuous smooth regulation
Accuracy: ±(1.5%x reading+10V)
Voltage Resolution: 1V

Test frequency

45, 50, 55Hz single frequency
45/55Hz automatic dual variable frequency
Frequency accuracy: ±0.01Hz

External HV

UST, maximum test current is 1A/ 40~70Hz
GST, maximum test current is 12kV/1A/40-70Hz

CVT self-excitation low voltage output

Output voltage 3~50V, output current 3~30A

Measuring duration

About 40s, depending on measuring method

Input power supply

180V~270VAC, 50Hz/60Hz±1%, supplied by alternating current or generator

Computer interface

Standard RS232 interface

Printer

WH-A7 mini-type thermal printer

Operating Temperature

-10℃~50℃

Relative humidity

<90%, Non-condensing

Overall dimension

340×260×270mm

Weight

22kg

 

4. Features

1). The instrument adopts complex number current method to measure capacitance, dielectric loss and other parameters. The measured result is highly accurate and it is easy to realize automatic measurement.

2). The instrument adopts variable frequency technology to eliminate 50Hz/60Hz power frequency interference. So a reliable data will be reachable even under the strong electromagnetic interference.

3). The instrument adopts large screen LCD . In the process of testing, Chinese menu prompt is visualized and easy to operate.

4). The instrument is easy to operate and the measuring process is controlled by microprocessor. Once a suitable measuring method is selected, the data measurement will complete automatically under the control of microprocessor.
 

5). The instrument is designed to be an integrated model with reference capacitor and HV power supply in it, enables site test measurement and reduces site wiring.

6). The instrument is equipped with CVT testing function, which can achieve CVT self-exciting testing without external accessories and measure the capacitance and dielectric loss of C1 and C2 by at a time.

7). GST measurement adopts ivddv technology and avoids unstable data provided by previous GST measurement.

8). The instrument provides low voltage shell function of GST. When the bus of 220kV CVT is grounded, Dielectric loss tester can be conducted for C11 without removing 10 kV GST.
 

9). The instrument has a function of measuring high-voltage dielectric loss. It can carry out dielectric loss test with over 12kV with the help of voltage transformer or series resonance.

10). The instrument has a ground-fault protection function. In case that the instrument is not grounded or grounded incorrectly, the instrument will refuse to enter into normal procedure and output HV. As for the over-current protection function, it will protect the instrument from damage when the tested article is in a short circuit or breakdowns.

11). The instrument has a function of electric shock protection. When the instrument operator suffers an electric shock due to incaution, the instrument will cut off the HV immediately and thus ensure the security of operator.

 

5. Stocks at office

tan delta test of transformer in stock (2)

 

6. Packing, Delivery, Shipping and Payment

deliver fuootech Capacitance Tan Delta Tester (2)

 

7. Certificates

FUOOTECH Inductive load Dc resistance tachometer certificate_

 

8. Our Advantages

1) 19 years experience in developping and manufacturing according to related China and internatinoal standards

2) Choose Higher quality raw material from the demostic and worldwide market

3) Own complete and advanced production facilities

4) Has the strict test procedures on raw materials and products from A to Z.

5) Have passed CE, ISO certificates

6) Longer warranty period for all our products (2 Years)

7) Factory Direct Sale, More competitive price

8) Variety types for selection and OEM & ODM are available

fuootech W.jpg

 

Over the years, the company has been at the forefront of China's Transformer Capacitance Dissipation Insulation Power Factor Tan Delta Test Set industry with its strong own technology and comprehensive capabilities. We hope to cooperate with you with an open attitude to maximize our interests and ultimately achieve a win-win situation. We will serve you with all sincerity!

Hot Tags: transformer capacitance and tan delta tester, China, suppliers, manufacturers, customized, price, in stock, buy discount, palm oil processing machine, transformer oil treatment equipment, Water Soluble Acid Analyzer, Offline hydraulic oil filtration systems, fuel oil purification plant, oil water separator