We persistently pursue perfect quality and use our unremitting efforts to become a trusted partner of Oil reconditioning system, two stage vacuum pump, insulating oil dielectric loss tester for customers! We strive to raise awareness of health, safety and health, and continuously improve our occupational health and safety management system. We strive to find the right fit with our customers' interests to achieve mutual benefits and create common values. All our employees unite their will and actions to seek the development of the company and create great achievements together. The company insists on starting from customer needs, taking customer satisfaction as the end result, integrating multiple technical resources, and establishing a complete process and network.
1. Introduction and Application
Series FYZ OLTC (On Load Tap Changer) Insulation Oil Purifier designed and produced by FUOOTECH Group since 2005 is mainly used as a bypass circulation filtering system of OLTC (the transformer high voltage switch.). It can timely filter the oil while the transformer operates normally, or it can automatically filter the oil after switching off the OLTC.
This equipment can efficiently remove the impurities, dissociated free carbon, water and oxides to ensure the quality of oil, thus it can guarantee the oil's insulation, increase the switching times, postpone the repairing period, decrease the power cut off times, ensure the voltage's quality and improve the safety and reliability of the OLTC.
2. Product Flow Chart
Purification flow: OLTC Oil Purifier → Oil inlet → Oil pump → Impurities filter → Dewatering filter → Oil outlet → OLTC oil purifier.
Small Online On-Load Tap Changer (OTLC) Transformer Oil Filtration Unit manufactured by FUOOTECH oil purifier company ensures that the related main electric equipment works safely during the maintenance period.
Online On-Load Tap Changer (OLTC) Transformer Oil Purification Unit can remove free carbon and metal debris during the normal operation of the transformer system, and reduce the moisture content in the tap changer oil, to ensure the breakdown voltage and service life of the oil, This improves the safety and reliability of the on-load tap-changer, thus extending the maintenance interval.
3. Technical Parameters
Item |
Name of Parameter |
Unit |
Model FYZ-10 |
Model FYZ-20 |
||
Technical Parameter |
Nominal flow rate |
L/min |
10 |
20 |
||
|
Working Pressure |
Mpa |
≤0.5 |
≤0.5 |
||
Power Supply |
|
380VAC, 50Hz, 3 Phase, 4 Wires, or as needed |
||||
Medium temperature |
℃ |
-45℃ ~ 115℃ |
||||
Noise |
dB (A) |
≤ 65 |
||||
Working Hours without trouble |
Hours |
≥ 9000 |
||||
Continuous Working Hours |
Hours |
≥ 720 |
||||
Total electric power |
KW |
0.45 |
0.75 |
|||
Diameter of inlet/Outlet hose |
DN mm |
15/15 |
25/25 |
|||
Dimension |
Length |
mm |
500 |
530 |
||
Width |
mm |
225 |
350 |
|||
Height |
mm |
750 |
1000 |
|||
Weight |
KGS |
55 |
88 |
|||
Oil Result after Filtration |
Filtering Accuracy |
micron |
≤ 1 |
≤ 1 |
||
Moisture (Water Content) |
PPM |
≤ 20 |
≤ 20 |
|||
Cleanness |
NAS level |
≤ 6 Grade NAS 1638 |
≤ 6 Grade NAS 1638 |
Note: 1. The dimension and weight will be changed with changing of technical specs.
2. All the specs can be customized according to client's requirements.
4. Features
1). Work online with on-load working transformer or high voltage switch.
2). High quality filters remove the particles, impurities and moisture effectively.
3). All-weather Structure Case and standard control box, Made of Stainless steel.
4). PLC with touch screen installed: Displaying the filter's status and machine operation status.
5). Positive and negative direction control of the motor, protection of over-load of motor start and phase-lacking.
6). Automatically run this machine once after the operation of OLTC, the operation time can be set according to requirement from 0-99 hours, but it is usually set as 30 minutes. Another way is to proceed the filtration works every day at a fixed time lasting two hours.
7). Small volume, light weight, low maintenance cost and time.
5. Our Main Customers and Partners
6. Packing, Delivery, Shipping and Payment
7. Onsite Projects
8. Certificates
9. Warm Notice on OLTC Transformer oil filtration plant
1) When the oil filter is not full of oil, it is strictly forbidden to start online
2) Before starting, the inlet and outlet valves of the oil filter and the switch must be in an open status
3) After the oil filter is installed or overhauled, the user is required to switch on for trial operation to prevent accidents
4) Never start the equipment when the oil inlet and outlet shut-off valve is closed
5) If it is found that the water content of the oil remains high, even if the alarm is not reported, the cause should be found out, the fault should be eliminated, and the water removal filter element should be replaced if necessary
6) The oil pipes must be cleaned after welding
7) Maure sure the inlet and outlet hoses are connected correctly
8) Make sure the cable connection and input voltage are correct
Our with Humidity Relay Oltc on-Line Transformer Oil Purifier of on-Load Taps Change for Transformer (BYL) competes with other manufacturers on the basis of quality, reliability, and especially the diversification of varieties. Our company has advanced production equipment, strong scientific and technological force, rich production experience and strict quality management system. It is a large-scale enterprise in the same industry in China. Long term brand building is our unremitting pursuit, so that every phone call, every service and every batch of distribution become the guarantee of quality and the embodiment of brand.
Hot Tags: oltc on load tap changer transformer oil purifier, China, suppliers, manufacturers, customized, price, in stock, buy discount, Transformer Oil DGA Tester, transformer oil purification vacuum degasifier, digital densometer, transformer winding resistance testing equipment, palm oil processing machinery, kinematic viscosity testing apparatus