We will create high-quality brands and create a monument of OLTC oil filtration, steam turbine lube oil purifier, Transformer Capacitance Tan Delta Tester industry and move forward forever. The company will make full use of the advantages of professional production to carry out extensive strategic cooperation with other enterprises. With reasonable price and satisfactory service, we are deeply trusted by many large and medium-sized enterprises at home and abroad.
1. Introduction
Transformer oil regeneration module ZYD-I developped by FUOOTECH enables complete renewal of used and old transformer oil onsite fulfilling the requirement of IEC 60422 standard.
ZYD-I oil reeneration plant only provides regular oil purification including degassing, drying and particulate removal but also removes acidity, sludge, other soluble oil decay products, and improves color. For special application, the system also can be mounted on a leak proof base or be installed and operated on a trailer.
2. Why Transformer Oil Need be Regenerated?
Most power equipments are using transformer oil for their dielectric properties for cooling, insulating, and protecting the active parts. Transformer oils are highly refined oils that consist mainly of a mixture of hydrocarbons. Over time, oxidation by products start to form in the oil. Increases in oxidation by products result in the increase of acidity (neutralization number) and decrease the interfacial tension of the oil. At this stage, sludge starts to form, and oil is losing its dielectric properties because it is getting old. To prevent further deterioration of oil and possible damage to the active part of the transformer, oil needs to be regenerated.
3. Oil Comparasion Before and After Regeneration
4. Technical Parameters
Item |
Unit |
ZYD-I-30 |
ZYD-I-50 |
ZYD-I-100 |
ZYD-I-150 |
ZYD-I-200 |
ZYD-I-250 |
ZYD-I-300 |
|
Flow rate |
L/h |
1800 |
3000 |
6000 |
9000 |
12000 |
15000 |
18000 |
|
Working vacuum |
MPa |
-0.08~-0.099 |
|||||||
Vacuum pressure |
MPa |
≤0.3 |
|||||||
Temperature range |
℃ |
20~80 |
|||||||
Power |
|
3ph 380V 50Hz(or as need) |
|||||||
Working noise |
dB(A) |
75 |
75 |
75 |
75 |
80 |
80 |
80 |
|
Heating power |
kW |
30 |
30 |
45 |
60 |
75 |
90 |
120 |
|
Total power |
kW |
35.5 |
37.5 |
52.5 |
71.4 |
86.5 |
102.5 |
135 |
|
Oil Inlet/Outlet |
mm |
φ25 |
φ32 |
φ42 |
φ50 |
φ50 |
φ60 |
φ60 |
|
Weight |
Kg |
600 |
800 |
1050 |
1400 |
1800 |
2000 |
2200 |
|
Overall |
Length |
mm |
1050 |
1100 |
1200 |
1450 |
1600 |
1800 |
1900 |
Width |
mm |
750 |
800 |
950 |
950 |
1100 |
1200 |
1200 |
|
Height |
mm |
1350 |
1400 |
1500 |
1650 |
1800 |
1900 |
1900 |
|
Breakdown Voltage |
kV |
≥75 |
|||||||
Moisture content |
PPM |
≤3 |
|||||||
Gas content |
% |
≤0.1 |
|||||||
Impurity size |
micron |
≤1 (no free carbon) |
|||||||
IFT |
dynes/cm |
≥40 |
|||||||
Acid value |
mg KOH/g |
≤ 0.03 |
|||||||
Dielectric loss factors |
tgδ(90℃) |
≤0.001 |
Note: 1. The dimension and weight will be changed with changing of technical specs.
2. All the specs can be customized according to client's requirements.
5. Features
1). For special application, the operation can be controlled by P.L.C (Programmable Logic Controller) .
2). Unique vacuum dehydration, degassification and regeneration system, adopt stereo-evaporation technology. Duplex 3D stereo-evaporation, eliminating the liquid water quickly
3). UK g technology by which the trace water that is show chain, such as dissolved water, can be removed effectively.
4). Advanced infrared liquid-level automatic control system to accomplish fully automatic control.
5). Can be applied for vacuum oiling and drying power transmission equipment.
6). Special additives for depolarization can recover oil color of aged transformer oil to new.
6. Our Main Customers and Partners
7. Packing, Delivery, Shipping and Payment
8. Onsite Projects
9. Certificates
10. Our Pre-sale Services
1) Communicated through email, phone, whatsapp, skype, etc., knowing your actual requirements and demands, remcommend you the most suitable model.
2) Related technical documents and commercial quotation can be sent within 4 hours.
3) We have many standard models in stock so they can be delivered within short time.
4) OEM and ODM order are accepted, Any kind of logo printing or design are available.
5) Good Quality + Factory Price + Quick Response + Reliable Service, is what we are trying best to offer you.
6) All the products are produced by our professional workman and our high-work-effect foreign trade team will solve all your problems from different language, time difference, etc.
We are in a leading position in the industry of Dielectric Transformer Oil Regeneration Plant for Used Tranformer Oil Renewable with advanced technological processes, high-quality product and preferential prices. We ensure the timeliness and effectiveness of work communication and implementation, and the timely reporting and feedback of work information. We will accelerate our nationwide strategic layout and market scale expansion.
Hot Tags: double-stage vacuum transformer oil regeneration system, China, suppliers, manufacturers, customized, price, in stock, buy discount, mini oil filter machine, transformer oil breakdown voltage tester, Transformer Turn Ratio Group Tester, transformer oil tan delta test set, sf6 analyzer, Transformer Loss Tester