We will continue to be serious and responsible attitude to provide customers with quality portable turbine oil purification system, Oil water content tester, 20000V Insulation Tester and services, customer smile is our affirmation. Our company has always adhered to the concept of "creating value for shareholders, providing opportunities for employees, and taking responsibility for society". Our company's environmental management fully implements the concept of environmental management, relies on the environmental management system, and observes the regulations and standards as the guidelines. Through our unremitting efforts, we enable our customers to obtain practical and psychological satisfaction from our products and services. Through cooperation with us, you and your business can feel our dedicated service to customers and unremitting pursuit of product quality.
1. Introduction & Application
FTKZ-50A Transformer On-No Load Characteristics Analyzer is the latest product of FUOOTECH Group. This transformer on load loss tester adopts the popular ARM processor in this year, with 168M basic frequency and 128m memory, which can be expanded to 4G memory card. Using 7-inch high-definition color touch panel, combined with emwin display interface so as to make the instrument interface being friendly and operated in a simple way, it can be operated through the touchscreen without keyboard. The instrument support database and can be exported through USB disk or transmitted to computer via data wire.
The circuit design of this instrument is exquisite and unique, which makes it superior in performance, powerful in function, small in size and light in weight. It can not only be used to test the on-no load parameters of transformer, but also measure the harmonic content and waveform in the field. The instrument can record the test curve of transformer under on-no load condition, then provide reliable basis for transformer fault analysis.
2. Why On Site Transformer Empty Load Characteristics Tester Load Loss Test of transformer is required?
Energy source in the world especially in the developping and undevelopped countries is more and more short, air pollution is more and more serious, which forwards higher requirement on energy saving of the power transformer. Whenever a power transformer is energized , its core will consume energy and this energy will be in form of heat and it is called no-lead losses, these losses will be always present whether the transformer carries load or not.
Loss measurement of the transformer at low power factor always makes the whole industry confused for many years, therefore it is only solved through procurement from developped country at high price.
FUOOTECH developped this Transformer Empty Load Test Bed Power Analyzer under strong support of National Science and Technology Fund after difficult investigation for many years. This high technology product with own intelligent property not only reaches international advanced level for precision measurement at low power factor, its innovative data automatic locking technology is characterized with accurate locking, no artificial interference, which can improve working efficiency tens times.
The instrument applies 7.0 inch colourful liquid crystal display screen and the intelligent touching control technology, operation is more convenient.
Performance of the instrument is excellent, which is extensively applied in motor and air fan, power, and other industries.
3. Technical Parameters
1) Voltage measurement scope: AC 10~1000V
2) Current measurement scope: AC 0.1 ~50 A
3) Measurement accuracy:
Voltage: 0.1%±0.005V (frequency 40~70Hz)
0.5%±0.005V (frequency 70~200Hz)
Current: 0.1%±0.0002A (frequency 40~70Hz)
0.5%±0.0002A (frequency 70~200Hz)
Power: P×0.1%± (U×I×0.02%) ±0.05W (P is power factor, U is reading of voltage effective value, I is reading of current effective value)
4) Working power supply: AC220V±10%, 50/60 Hz
5) Working temperature: -20℃~40℃
6) Relative humidity: ≤80%RH no dewing
7) Volume: 360×360×200mm
8) Weight: 12kg
4. Functions and Features
1). It can measure voltage, current, angle, power and other electrical parameters, and it also can display the vector diagram of voltage and current, both of the displays are shown clearly and intuitively on the same screen.
2). It can measure the parameters such as no-load loss, load loss and impedance voltage, etc.
3). The instrument has the function of harmonic analysis. It can measure the 1-32 harmonic content of voltage and current applied to transformer and display bar graph as well as voltage and current waveform.
4). The on-no characteristic curve under different voltage and current can be recorded automatically during the test process of on-no load condition of transformer, which can be more convenient to analyze the characteristics of transformer and core.
5). With the function of data storage and data browsing, the instrument supports DBF database, and it can store test data or browse test records according to user requirements. The instrument also supports the USB disk export function, you can export the test data through USB disk, and the database supports the excel spreadsheet opening mode, which is convenient for editing, printing or archiving.
6). Operate with 7-inch true color touch screen, the GUI interface, with build-in 128M memory (extensible 4G memory card), it supports English and is easy to operate.
7). It is small in size, light in weight, accurate in measurement, no power off calendar and clock function, so it can store test time at any time.
5. Stocks at office
6. Packing, Delivery, Shipping and Payment
7. Certificates
8. Packing List
No. |
Item |
Qty |
1 |
Main engine |
1 |
2 |
Power line |
1 |
3 |
Ground lead |
1 |
4 |
Touch Pen |
1 |
5 |
Fuse pipe |
2 |
6 |
Print paper |
1 |
7 |
Voltage line |
1 |
8 |
Current line |
1 |
Every single member from our higher effectiveness product sales staff values customers' requires and organization communication for Factory Direct Transformer Capacity Loss Test Equipment/Transformer No-Load Current Tester. The internal team of our own value can play a key role in the company's business. We adhere to the people-oriented, continuous exploration and the pursuit of science and efficiency.
Hot Tags: transformer empty load characteristics analyzer, China, suppliers, manufacturers, customized, price, in stock, buy discount, transformer oil purifier machine, Acid Value Tester, Plate Frame Press Oil Purifier, dielectric strength testing equipment, CT voltage current characteristic integrated tester, oil bdv tester