FUOOTECH Oil Purifier & Testing Equipment Manufacturing Group's FTD-6000A Automatic Transformer Dissipation Factor and Capacitance Tester breaks through the traditional bridge measurement mode, adopts frequency conversion power supply technology, uses single chip computer and modern electronic technology to automatically convert frequency, analog/digital conversion and data operation; achieves strong anti-interference ability, fast testing speed,high accuracy, fully automatic digitization and easy operation; automatic filter 50Hz interference, suitable for field testing of large electromagnetic interference such as substations.
It is widely used in dielectric loss measurement of transformer, transformer, bushing, capacitor, arrester and other equipment in power industry.

Technical Parameters
|
Accuracy |
Cx: ±(reading×1%+1pF) |
|
Anti-interference Index |
Variable frequency anti-interference, the above accuracy can be reached even under 200% interference. |
|
Capacitance range |
Internal HV: 3pF~60000pF/10kV 60pF~1μF/0.5kV |
|
tgδ range |
No limitation, 0.001% resolution, |
|
Test current range |
10μA~5A |
|
Internal HV |
Set voltage range: 100V~10kV (adjustable) Maximum output current: 200mA |
|
External HV |
UST test mode: max. test current: 5A, frequency: 40~70Hz |
|
Test frequency |
40.0 ~ 70.0Hz single frequency, resolution: 0.1Hz Automatic dual variable frequency set at will (from 60±0.1Hz to 60±10Hz) |
|
CVT self-excitation low voltage output |
Output voltage 3~50V, output current 3~30A |
|
Measuring duration |
About 40s, depending on measuring method |
|
Power supply |
220V AC, 50Hz ± 1% |
|
Computer interface |
RS232, USB |
|
Printer |
Built-in mini-type thermal printer |
|
Operating Temperature |
-10℃~50℃ |
|
Relative humidity |
<90% |
|
Overall dimension |
520×210×440mm |
|
Weight |
31kg |